PROWLER SPECIFICATIONS

Model #:

LD 5000

Name:

PROWLER Leak Detector, Refrigerant Gas

Sensitivity:

0.025 oz/yr R-22, 0.05 oz/yr R-134a,

0.0125 oz/yr R-1234yf, 0.05 oz/yr R-410A,

0.05 oz/yr R-404A,

0.05 oz/yr R-407A,

0.05

oz/yr

R-427A

Sensor Life:

> 10 years (normal use)

Response Time:

Instantaneous

Power Supply:

4 AA Alkaline batteries

Battery Life:

4.5 hours continuous

Warm Up Time:

< 20 seconds

Probe Length:

17”

LCD Display:

Sensitivity, Battery Light, Leak Level Indication

Weight, lbs.:

1lb. 3.4 oz.

Warranty:

2 years includes sensor

EN 14624 TEST SPECIFICATIONS

Min/Max Sensitivity

1 gm/yr minimum, > 50 gr/yr maximum

Threshold (fi xed):

Min/Max Sensitivity

3 gm/yr minimum, > 50 gm/yr maximum

Threshold (moving):
Min Detection Time:

Approximately 1 second

Clearing Time:

Approx. 9 seconds after exposure to > 50 gm/yr

Min. Threshold after
Maximum Exposure:

1 gr/yr

Sensitivity Threshold in
Polluted Atmosphere: 1 gm/yr
Calibration Frequency: 1/yr check with calibrated leak Standard