SAE-1111/1112/1162 Carbon Monoxide (CO) Detectors

5

Installation Guide

When a value is changed, press the <SAVE> key to

save it to memory and advance to the next menu

item.

Press <MENU>

CO Range = 0–300 ppm

Press the <ROLL> key to scroll through the avail-

able options. The CO sensing range and output

scale can be changed to 0 to 100 ppm, 0 to 150

ppm, 0 to 300 ppm, 0 to 400 ppm, or 0 to 500 ppm.

Press the <SAVE> key to save any change. The

factory default CO Range is 0 to 300 ppm.

Press <MENU>

Buzzer = Enable

Use the <ROLL> key to enable or disable the

buzzer alarm. When disabled, the buzzer will not

sound if the buzzer trip point is exceeded. The

buzzer will still beep on startup and will still beep

for a fault alarm (if enabled). Press <SAVE> to

save the setting. The factory default is Enable.

Press <MENU>

Buzzer Trip = 150

Use the <ROLL> key to scroll through the avail-

able options. The buzzer alarm trip point may be

set from 0 to 500 ppm in 10 ppm increments. Press

<SAVE> to save the setting. The factory default

is 150 ppm. (This item will not be shown if the

buzzer is disabled.)

Press <MENU>

Buzzer Del = 5Min

Use the <ROLL> key to scroll through the avail-

able options. The buzzer delay may be set from

0 to 10 minutes in 1 minute increments. Press

<SAVE> to save the setting. The factory default

is 5 minutes. (This item will not be shown if the

buzzer is disabled.)

Press <MENU>

Buzzer Test = OFF

Use the <ROLL> key to enable the buzzer (ON)

during test mode or disable it (OFF). Press

<SAVE> to save the setting. The factory default is

Off. (This item will not be shown if the buzzer is

disabled.)

Press <MENU>

Relay 1 TRIP = 50

Use the <ROLL> key to scroll through the avail-

able options. The Relay 1 alarm trip point may

be set from 20 to 500 ppm in 10 ppm increments.

Press <SAVE> to save the setting. The factory

default is 50 ppm. (This item will not be shown if

Relay 1 is not installed.)

Press <MENU>

Relay 1 Hyst = 10

Use the <ROLL> key to scroll through the avail-

able options. The Relay 1 hysteresis (deadband)

may be set from 10 to 100 ppm in 5 ppm incre-

ments. Press <SAVE> to save the setting. The

factory default is 10 ppm. Note that the maximum

value may be limited by the trip-point value. (This

item will not be shown if Relay 1 is not installed.)

Press <MENU>

Relay 1 DEL = 2MIN

Use the <ROLL> key to scroll through the avail-

able options. The Relay 1 delay may be set from

0 to 10 minutes in 1 minute increments. Press

<SAVE> to save the setting. The factory default is

2 minutes. (This item will not be shown if Relay 1

is not installed.)

Press <MENU>

Relay 1 Test = OFF

Use the <ROLL> key to enable Relay 1 (ON) dur-

ing test mode or disable it (OFF). Press <SAVE>

to save the setting. The factory default is Off. (This

item will not be shown if Relay 1 is not installed.)

Press <MENU>

Relay 2 Trip = 150

Use the <ROLL> key to scroll through the avail-

able options. The Relay 2 alarm trip point may

be set from 20 to 500 ppm in 10 ppm increments.

Press <SAVE> to save the setting. The factory

default is 150 ppm. (This item will not be shown if

Relay 2 is not installed.)