SAE-1111/1112/1162 Carbon Monoxide (CO) Detectors
5
Installation Guide
When a value is changed, press the <SAVE> key to
save it to memory and advance to the next menu
item.
Press <MENU>
CO Range = 0–300 ppm
Press the <ROLL> key to scroll through the avail-
able options. The CO sensing range and output
scale can be changed to 0 to 100 ppm, 0 to 150
ppm, 0 to 300 ppm, 0 to 400 ppm, or 0 to 500 ppm.
Press the <SAVE> key to save any change. The
factory default CO Range is 0 to 300 ppm.
Press <MENU>
Buzzer = Enable
Use the <ROLL> key to enable or disable the
buzzer alarm. When disabled, the buzzer will not
sound if the buzzer trip point is exceeded. The
buzzer will still beep on startup and will still beep
for a fault alarm (if enabled). Press <SAVE> to
save the setting. The factory default is Enable.
Press <MENU>
Buzzer Trip = 150
Use the <ROLL> key to scroll through the avail-
able options. The buzzer alarm trip point may be
set from 0 to 500 ppm in 10 ppm increments. Press
<SAVE> to save the setting. The factory default
is 150 ppm. (This item will not be shown if the
buzzer is disabled.)
Press <MENU>
Buzzer Del = 5Min
Use the <ROLL> key to scroll through the avail-
able options. The buzzer delay may be set from
0 to 10 minutes in 1 minute increments. Press
<SAVE> to save the setting. The factory default
is 5 minutes. (This item will not be shown if the
buzzer is disabled.)
Press <MENU>
Buzzer Test = OFF
Use the <ROLL> key to enable the buzzer (ON)
during test mode or disable it (OFF). Press
<SAVE> to save the setting. The factory default is
Off. (This item will not be shown if the buzzer is
disabled.)
Press <MENU>
Relay 1 TRIP = 50
Use the <ROLL> key to scroll through the avail-
able options. The Relay 1 alarm trip point may
be set from 20 to 500 ppm in 10 ppm increments.
Press <SAVE> to save the setting. The factory
default is 50 ppm. (This item will not be shown if
Relay 1 is not installed.)
Press <MENU>
Relay 1 Hyst = 10
Use the <ROLL> key to scroll through the avail-
able options. The Relay 1 hysteresis (deadband)
may be set from 10 to 100 ppm in 5 ppm incre-
ments. Press <SAVE> to save the setting. The
factory default is 10 ppm. Note that the maximum
value may be limited by the trip-point value. (This
item will not be shown if Relay 1 is not installed.)
Press <MENU>
Relay 1 DEL = 2MIN
Use the <ROLL> key to scroll through the avail-
able options. The Relay 1 delay may be set from
0 to 10 minutes in 1 minute increments. Press
<SAVE> to save the setting. The factory default is
2 minutes. (This item will not be shown if Relay 1
is not installed.)
Press <MENU>
Relay 1 Test = OFF
Use the <ROLL> key to enable Relay 1 (ON) dur-
ing test mode or disable it (OFF). Press <SAVE>
to save the setting. The factory default is Off. (This
item will not be shown if Relay 1 is not installed.)
Press <MENU>
Relay 2 Trip = 150
Use the <ROLL> key to scroll through the avail-
able options. The Relay 2 alarm trip point may
be set from 20 to 500 ppm in 10 ppm increments.
Press <SAVE> to save the setting. The factory
default is 150 ppm. (This item will not be shown if
Relay 2 is not installed.)