KMC Controls SAE-1162 User Manual

Page 6

Advertising
background image

SAE-1111/1112/1162 Carbon Monoxide (CO) Detectors

6

Installation Guide

Press <MENU>

Relay 2 Hyst = 20

Use the <ROLL> key to scroll through the avail-

able options. The Relay 2 hysteresis (deadband)

may be set from 10 to 100 ppm in 5 ppm incre-

ments. Press <SAVE> to save the setting. The

factory default is 20 ppm. Note that the maximum

value may be limited by the trip-point value. (This

item will not be shown if Relay 2 is not installed.)

Press <MENU>

Relay 2 Del = 2Min

Use the <ROLL> key to scroll through the avail-

able options. The Relay 2 delay may be set from

0 to 10 minutes in 1 minute increments. Press

<SAVE> to save the setting. The factory default is

2 minutes. (This item will not be shown if Relay 2

is not installed.)

Press <MENU>

Relay 2 Test = OFF

Use the <ROLL> key to enable Relay 2 (ON) dur-

ing test mode or disable it (OFF). Press <SAVE>

to save the setting. The factory default is Off. (This

item will not be shown if Relay 2 is not installed.)

Press <MENU>

TestMode = Disable

Use the <ROLL> key to disable or enable the

test mode. The factory default is Disable. When

disabled, the TEST button or TEST input will not

initiate the test function. When enabled, pressing

the TEST button or shorting the TEST input will

initiate the test function. Press <SAVE> to save the

setting.

Press <MENU>

TestMode = Time 5

Use the <ROLL> key to scroll through the avail-

able options. The test mode operating time may be

set from 1 to 15 minutes in 1 minute increments.

Press <SAVE> to save the setting. The factory

default is 5 minutes. This item sets how long the

test mode will operate when the TEST button is

pressed. (This item is not shown if the test mode is

disabled.)

Press <MENU>

Fault Md = Disable

Use the <ROLL> key to select Enable, Disable, or

Reset. When disabled, the device will not sound

the buzzer or provide LCD and status LED in-

dication when the sensor life is exceeded. When

enabled, the fault alarm will activate to indicate the

sensor life is exceeded. Press <SAVE> to save the

setting. The factory default is Disable. If it is set to

Reset and <SAVE> is pressed, then the fault condi-

tion is cleared, the life-time timer is reset and fault

mode is set back to its default (Disable). It may be

enabled again.

WARNING

All commercial CO sensors have a finite life. The
life expectancy of these models is 5 to 7 years.
They must be replaced periodically to ensure
reliable operation in detecting conditions that are
potentially hazardous to human health and safety.

Press <MENU>

Fault Md Time = 3yr

Use the <ROLL> key to set the fault mode timer

to 3, 4, 5, or 6 years. The factory default is 3 years.

Press <SAVE> to save the setting. If the desired

time has already been exceeded, then it cannot be

selected. (This item is not shown if the fault mode

is disabled.)

Press <MENU>

ReCal Md = Enable

Use the <ROLL> key to select Enable, Disable, or

Reset. When disabled, the device will not sound

the buzzer or provide LCD and status LED indica-

tion when the sensor requires recalibration. When

enabled, the ReCal alarm will activate to indicate

the sensor requires recalibration. Press <SAVE>

to save the setting. The factory default is Enable.

If set to Reset and <SAVE> is pressed, then the

ReCal condition is cleared, the ReCal timer is

reset, and ReCal mode is set back to its default

(enabled). This can be used if the CO sensor is

required to be recalibrated at known intervals.