Planning for motion sensing

Typical motion sensing coverage

55°

10 m

32.8 ft

10 m

32.8 ft

X

0°

10 m

32.8 ft

10 m

32.8 ft

0°

46.5°

Y

Motion sensor vertical and horizontal patterns

Side view

Top view

For motion sensing models only—Mount the sensor

on a wall that will have an unobstructed view of the

typical traffic in the coverage area. When choosing

a location, do not install the sensor in the following

areas.

◆

◆

Behind curtains or other obstructions

◆

◆

In locations that will expose it to direct sunlight or

heat sources

◆

◆

Near a heating or cooling inlet or outlet.

The effective detection range is approximately 10

meters or 33 feet. Factors that may reduce the range

may include the following items.

◆

◆

The

difference between the surface temperature of

the object and the background temperature of the

room is too small.

◆

◆

Object movement in a direct line toward the

sensor.

◆

◆

Very slow or very fast object movement.

◆

◆

Obstructions in the shaded area of the diagram

Typical motion sensing coverage.

False detections may be triggered by any of the

following conditions.

◆

◆

The temperature inside the detection range

suddenly changes because of the entry of cold or

warm air from an air-conditioning or heating unit.

◆

◆

The sensor being directly exposed to sunlight, an

incandescent light, or other source of far-infrared

rays.

◆

◆