KMC Controls MEP-4101 User Manual

Installation guide, Direct-coupled controlset, Actuator (10 in-lb.)

Advertising
background image

MEP-4101

1

Installation Guide

Installation Guide

Direct-Coupled ControlSet

®

Actuator (10 in-lb.)

MEP-4101

Mounting

1

Wiring

2

Maintenance

2

Accessories

2

Specifications 2

Mounting

1. Ensure the damper can

move freely through its

entire range of motion,

and fix any binding

before installing the

actuator. Turn the

damper blade to its

fully closed position.

2. Press (to the right)

and hold the gear

disengagement lever

(see the illustration),

rotate the actuator to the

fully closed position,

and release the lever.

NOTE: Depending on

the damper-seal

design, backing

the actuator

off its stop

approximately 5°

may provide tight

damper shut-off.

3. Align the actuator and

slide it onto the shaft.

4. Leaving a gap between

the actuator and

mounting surface to

prevent any binding,

finger-tighten the nuts

on the V-bolt.

5a. Insert the non-rotation

bracket (HMO-4002

supplied or HMO-4001

“T” bracket available

separately) into the

slot at the base of the

actuator and secure the

non-rotation bracket

with two #8 or #10 self-

tapping screws. (This

is the recommended

method.)

5.313

135

3.844

97.6

1.281

32.5

0.204

0.194

5.18

4.93

LEDs VISIBLE UNDER TRANSLUCENT COVER
GREEN: POWER OPEN (CCW DIRECTION)
RED: POWER CLOSED (CW DIRECTION)

ADJUSTABLE

STOP

1.568

40

[63.5]

2.500

2.600

66

GEAR

DISENGAGEMENT

LEVER

All dimensions are in inches (mm)

HMO-4002

Non-rotation

Bracket (Provided)

Advertising