Wiring, Maintenance, Accessories – KMC Controls MEP-4101 User Manual

Page 2: Specifications, Specifications 2

Advertising
background image

MEP-4101

2

Installation Guide

© 2012 KMC Controls, Inc.

036-019-03A

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com

[email protected]

Maintenance

No routine maintenance is required. The motors

are permanently lubricated and all internal gear-

train components are oil-impregnated. Careful

installation will also ensure long term reliability and

performance.

Wiring

Connect the wires to the terminal block and apply 24

VAC (+20%/–15%) power for tri-state operation.

5.313

135

3.844

97.6

1.281

32.5

0.204

0.194

5.18

4.93

LEDs VISIBLE UNDER TRANSLUCENT COVER
GREEN: POWER OPEN (CCW DIRECTION)
RED: POWER CLOSED (CW DIRECTION)

ADJUSTABLE

STOP

1.568

40

[63.5]

2.500

2.600

66

GEAR

DISENGAGEMENT

LEVER

When the actuator reaches the end of rotation, the

motor is disengaged, and (after about five seconds)

the appropriate LED indicator under the translucent

cover illuminates—green for “power open” (CCW)

or red for “power closed” (CW). The LED remains

on until:
• Power to the terminal is simply removed
• Power is switched to the other terminal, and

the actuator starts turning again in the opposite

direction

Accessories

HCO-1151

Weather shield kit

HMO-4001

Non-rotation “T” bracket

HMO-4002

Replacement non-rotation

bracket

Supply Voltage

24 VAC (+20%/–15%), Class 2

Supply Power

2 VA

Control Signal

Tri-state, 24 VAC

Frequency

50/60 Hz

Angular Rotation

0 to 95°, fully adjustable with

mechanical stop

Motor Timing

30 seconds for 90° @ 60 Hz;

36 seconds for 90° @ 50 Hz

Torque

10 in-lb. (1.1 N•m)

Mounting

Direct on 1/4 to 5/8 inch (6 to

16 mm) round or 1/4 to 7/16

inch (6 to 11 mm) square shaft

by adjustable “V” bolt; mini-

mum recommended damper

shaft length is 1-5/8 inches

Connections

Wire clamp type; 14 to 22

AWG, copper

Dimensions

5.3 x 2.6 x 2.5 inches

(135 x 66 x 63.5 mm)

Weight

1 lb. (0.45 kg)

Enclosure

Flame-retardant plastic black

base and translucent cover

Noise Level

< 35 dBA max. at 1 meter

Environmental Limits

Operating

–22 to 140° F (–30 to 60° C)

Shipping

–40 to 176° F (–40 to 80° C)

Humidity

5 to 95% RH (non-condensing)

Specifications

5b. Alternately, insert a single #8 or #10 self-tapping

screw directly into the non-rotation slot. Tighten

the screw only enough to ensure that the screw

will not come out. There should be a bit a play

between the screw and the sides of the slot to help

prevent binding.

6. Evenly tighten the V-bolt nuts 30 to 35 in-lb.
7. If desired, use a 7/64-inch hex key wrench to

loosen and position the end-stop screw.