MEP-4000/4800 Series

2

Installation Guide

Illustration 3—MEP-4xx1/4x13 TRI-STATE Wiring

Illustration 4—MEP-4xx1/4x13 2-POSITION (3-Wire) Wiring

Illustration 5—MEP-4xx2 Proportional Wiring

Wiring

NOTE: Before January 2014, MEP-40x2/48x2

models had 0–10 VDC inputs. They now

have 2–10 VDC inputs. When replacing

an older 0–10 VDC actuator with a 2–10

VDC actuator, configure the connected

controller or thermostat output to match.

See the model number on the actuator label and the

relevant wiring illustration (2 through 5).

MEP-4003 Only

NOTE: The MEP-4003’s terminals are not enclosed

inside the case as the other models are.

1. Route the cable through the strain relief molded

in the lower left of the case. (See Illustration 2.)

2. Connect the wires to the terminal block.

Illustration 2—MEP-4003 (Only) Wiring

All Except MEP-4003

1. Loosen the screw on the tethered access cover and

remove the cover.

2. Slide the conduit fitting plate out.
3. Using a utility knife or drill, cut the red plug

to accept wiring or replace the plug with an

application-specific fitting.

NOTE: The red plug (or similar fitting) protects

internal components from debris, helping to

ensure long actuator life.

4. Thread wires through the plugged opening and

connect to the terminal block. (See Illustrations 3

through 5.)

NOTE: For your convenience, the wiring terminal

block is removable.

5. Connect and adjust the auxiliary switch if

required (MEP-4x2x only). See

Auxiliary Switch

(4x2x) on page 4

.

6. Reinstall the terminal block on the pins (if

removed) and the conduit fitting plate.

7. For MEP-4xx2 (proportional) models, adjust the

auto-mapping range reset, rotation direction, and

feedback voltage as needed. See Illustration 5 and

Direction, Feedback, and Auto-Mapping (MEP-

4xx2) on page 3

.

8. For MEP-4xx1/4x13s, adjust rotation direction

switch if needed (see Illustration 3 and 4).

9. Reinstall the tethered cover and tighten the screw.

CW

COM
CCW

Switch Position:
1 = Rotation is
Direct
0 = Rotation is
Reversed

~

Feedback Potentiometer

(MEP-4x13 Only)

Power

Supply

CW

COM
CCW

Feedback Potentiometer

Switch Position:
1 = Rotation is
Direct
0 = Rotation is
Reversed

Contact Position: Open = CW Rotation, Closed = CCW Rotation

(MEP-4x13 Only)

~

Power

Supply

Power

Supply

~

+

Control Signal

2–10 VDC

+ Feedback Output

1–5 or 2–10 VDC

~

Power Supply

Strain Relief