Direction, Feedback, and Auto-Mapping (MEP-4xx2)

MEP-4xx2 models also offer a actuator/signal range

reset program (auto-mapping) feature that reassigns

the full 2–10 VDC input signal scale over a reduced

stroke range for more precise control.
NOTE: The auto-mapping feature works best for

ranges that are more than about 45°.

To set the auto-mapping:
1. If desired, use a 7/64-inch hex key wrench to

loosen and position the end-stop screw.

2. With power applied to the actuator, flip selector

switch #2 (from its required CW or CCW

increasing voltage direction) to start the reset

mode. The actuator will first move to the CCW

limit. The complete reset process will take

approximately four minutes.

3. Return selector switch #2 to the required

increasing voltage direction before the reset

finishes. The reset process is complete after the

actuator has moved to the CW limit and has

begun to position normally.

4. Verify that the actuator travels completely across

the new range.

For example, after completing the auto-mapping

program, the new actuator stroke is 0–80°:
• For current (starting Jan. 2014) MEP-40x2/48x2

actuators, a 6 VDC input signal (halfway between

2–10 VDC) will drive the actuator to the 40°

position (50% of its adjusted range) and the

feedback voltage will be 3 VDC if switch #1 is set

at the 1–5 VDC position or 6 VDC if switch #1 is

set at 2–10 VDC.

• For older

(before 2014) MEP-40x2/48x2 actuators,

a 5 VDC input signal (halfway between 0–10

VDC) will drive the actuator to the 40° position

(50% of its adjusted range) and the feedback

voltage will be 2.5 VDC if switch #1 is set at the

0–5 VDC position or 5 VDC if switch #1 is set at

0–10 VDC.

MEP-4xx2 proportional models offer selectable

actuator direction and selectable proportional feed-

back of 1–5 VDC or 2–10 VDC (in either direction).
To access the selector switches, loosen the screw on

the tethered cover and remove the cover. The selec-

tor switches are shipped from the factory in the 1–5

VDC (#1) and CW movement with increasing voltage

(#2) positions (see Illustration 6).

Illustration 6—Feedback/Direction/Mapping Selectors

*NOTE: Selector Switch #2 has two functions:

1. Switch #2 determines the direction to rotate

(CW or CCW) with increasing voltage and is

factory set in the CW position (down). To

change, remove power before flipping the

switch up to the CCW position. Removing

power prevents initiation of the auto-mapping

feature.

2. Switch #2 initiates the auto-mapping

feature. (See description below.) This feature

is initiated only by cycling the switch with

power applied to the unit. The auto-mapping

feature will NOT begin if the switch position is

changed with power removed or in the event

of a power failure.

Switch (#1) Feedback

(#2)* Direction

Up

1–5 VDC

CCW

Down

2–10 VDC

CW

NOTE: Before Jan. 2014, MEP-40x2/48x2 models

had 0–10 VDC inputs and 0–5 or 0–10

VDC feedback instead. When replacing an

older 0–10 VDC actuator with a 2–10 VDC

actuator, make note of the differences.

NOTE: For more information (including

adjustments, accessories, troubleshooting,

torque selection, and links to sample

applications), see the

MEP-4xxx

Applications Guide