3.2.8
Digital Input Menu
XXXXXXX
XXXXXXX
XXXXXXX
XXXXXXX
DIGIN1
OFF
DIGIN2
ZERO
T ARE
NT/GRS
UNITS
DSPTAR
CLRCN
OFF
ZERO
T ARE
NT/GRS
UNITS
DSPTAR
CLRCN
ALGOUT
DIGI N
SETPNT
PROGRM PFORMT
SERIAL
CALIBR
CONFIG FORMAT
HOLD
HOLD
KBDLOC KBDLOC
VERS
CLRTAR
CLRTAR
CLRACC
CLRACC
ACCUM
NEWID
ACCUM
NEWID
Figure 3-12. Digital Input Menu
Table 3-8. Digital Input Menu Parameters
DIG IN Menu
Parameter
Choices
Description
Level 2 submenus
DIGIN1
DIGIN2
OFF
ZERO
TARE
NT/GRS
UNITS
DSPTAR
PRINT
CLRCN
KBDLOC
HOLD
CLRTAR
ACCUM
CLRACC
NEWID
Specifies the function activated by digital inputs 1 and 2.
• ZERO, NT/GRS (net/gross mode toggle), TARE, UNITS, and PRINT provide the same
functions as the front panel keys.
• DSPTAR displays the current tare value.
• CLRCN resets the consecutive number to the value specified on the CONSTU parameter
(PROGRM menu).
• KBDLOC disables the keypad while the digital input is held low.
• HOLD holds the current display. Releasing this input clears the running average filter.
• CLRTAR clears the tare.
• ACCUM displays the accumulator.
• CLRACC clears the accumulator.
• NEWID enters the ID number.