Tjernlund UCRT Rooftop Inducer Universal Control (Version X.06) 8504162 Rev A 05/11 User Manual

Page 10

Advertising
background image

9

UC1 UNIVERSAL CONTROL CONNECTED TO A GAS OR OIL BURNER WITH AN AQUASTAT

XN

R

UN

IV

ER

SA
L CO

NT
RO

L

L

E

R

LINE VOLTAGE OIL BURNER

PRIMARY CONTROL, BURNER

L1

N

XL

J1

J2

115V

DRY

24V

AQUASTAT

B2

B1

C1

C2

L1

L2

D/N 9183046-7

115 VAC

LEGEND:

CALL
JUMPER

RELAY OR GAS VALVE

50/60 Hz

SUPPLY
115 VAC

RED JUMPER POSITION MUST BE THE SAME

IMPORTANT:

AS APPLIANCE INTERLOCK VOLTAGE.

SPADE TERMINAL IN ELECTRICAL BOX.

GROUND

CRIMP GROUND WIRE TO GROUNDING

IMPORTANT:

1. Disconnect B1 from L1 of oil burner primary control, burner relay or hot of gas valve and reconnect to #1 on UC1 terminal block.
2. Connect #2 on UC1 terminal block to B2 or N.
3. Connect #4 on UC1 terminal block to the L1 on line voltage oil burner primary control, burner relay or gas valve.
4. Make sure RED voltage jumper on UC1 is on 115V.
5. Connect 115 VAC supply voltage to L & N terminals on UC1. Connect the 2 green ground wires in UCRT to supply ground.

Important: Installer must supply overload and disconnect protection.

6. If not previously completed, connect Black, White and Red leads from UCRT to like colors in Rooftop Inducer whip 4x4 weather-

proof junction box. Connect the Green/Yellow ground lead in UCRT to the ground screw in the Rooftop Inducer whip 4x4
weatherproof box. Connect Blue and Yellow leads from UCRT to PSA-1 Fan Prover switch. Prover Leads are not polarity sensitive.

NOTE: If burner safety control goes out on lockout, the Inducer will continue to run as long as a call for heat is present.

UC1 UNIVERSAL CONTROL CONNECTED TO A HONEYWELL R7184 SERIES OR EQUIVALENT

PRIMARY CONTROL WITH A LINE VOLTAGE THERMOSTAT OR AQUASTAT

Burner

Alarm

Cad Cell

A

Interrupted

Intermittant

Motor

A

IGNITION TRANS

BURNER MOTOR

R

Oil Valve

Limit

R7184

L1

T

T

L2

OIL VALVE

115 VAC

60 Hz

SUPPLY

Limit

24
V

DRY

1

15V

XL

UNIVERSAL

CONT

ROL

L

E

R

XN

J1

J2

RED JUMPER POSITION MUST BE THE SAME

AS APPLIANCE INTERLOCK VOLTAGE.

IMPORTANT:

D/N 9183046-6

115 VAC

LEGEND:

CALL
JUMPER

Ignitor

Line Voltage Thermostat

or Aquastat Control

Low Voltage
Jumper

50/60 Hz

SUPPLY
115 VAC

SPADE TERMINAL IN ELECTRICAL BOX.

GROUND

CRIMP GROUND WIRE TO GROUNDING

IMPORTANT:

1. Disconnect burner motor wire off the R7184 and connect burner motor terminal of R7184 to #1 on UC1 terminal block.
2. Connect #2 on UC1 terminal block to L2 or N.
3. Connect #4 on UC1 terminal block to burner motor wire removed from R7184.
4. Make sure RED voltage jumper on UC1 is on 115V.
5. Connect 115 VAC supply voltage to L & N terminals on UC1. Connect the 2 green ground wires in UCRT to supply ground.

Important: Installer must supply overload and disconnect protection.

6. If not previously completed, connect Black, White and Red leads from UCRT to like colors in Rooftop Inducer whip 4x4 weather-

proof junction box. Connect the Green/Yellow ground lead in UCRT to the ground screw in the Rooftop Inducer whip 4x4
weatherproof box. Connect Blue and Yellow leads from UCRT to PSA-1 Fan Prover switch. Prover Leads are not polarity sensitive.