Tjernlund UCRT Rooftop Inducer Universal Control (Version X.06) 8504162 Rev A 05/11 User Manual

Page 11

Advertising
background image

10

UC1 UNIVERSAL CONTROL CONNECTED TO AN OIL-FIRED FURNACE WITH A

HONEYWELL T87 OR EQUIVALENT NON-POWERED THERMOSTAT

XN

R

UNIV

E

RS

A

L

CO

NTRO

LLE

R

REMOVE JUMPER TO AVOID

AS APPLIANCE INTERLOCK VOLTAGE.

RED JUMPER POSITION MUST BE THE SAME

XL

J1

J2

DRY

115V

24V

IMPORTANT:

BACKFEEDS OR SHORT

50/60 Hz

SUPPLY
115 VAC

NON-POWERED THERMOSTAT

F

F

T

T

D/N 9183047-1

PRIMARY CONTROL

SPADE TERMINAL IN ELECTRICAL BOX.

GROUND

CRIMP GROUND WIRE TO GROUNDING

IMPORTANT:

OR EQUIVALENT

5 VDC BOARD-GENERATED

LEGEND:

115 VAC

DO NOT SUPPLY POWER!

POWER.

LOW VAC

HONEYWELL T87 OR EQUIVALENT

W

O

WHITE

ORANGE

B

BLACK

HONEYWELL

R8184 SERIES

IMPORTANT:

FACTORY-

WIRED

CIRCUITS.

1. IMPORTANT: Remove J1 & J2 Call Jumper on UC1 to avoid backfeeds or short circuits.
2. Connect T87 or Equivalent non-powered thermostat to A and B terminals on UC1.
3. Remove T T Jumper from R8184 or equivalent Primary Control.
4. Connect #3 on UC1 terminal block to T terminal of Primary Control.
5. Connect #4 on UC1 terminal block to remaining T terminal of Primary Control.
6. Make sure RED voltage jumper on UC1 is on DRY.
7. Connect 115 VAC supply voltage to L & N terminals on UC1. Connect the 2 green ground wires in UCRT to supply ground.

Important: Installer must supply overload and disconnect protection.

8. If not previously completed, connect Black, White and Red leads from UCRT to like colors in Rooftop Inducer whip 4x4 weather-

proof junction box. Connect the Green/Yellow ground lead in UCRT to the ground screw in the Rooftop Inducer whip 4x4
weatherproof box. Connect Blue and Yellow leads from UCRT to PSA-1 Fan Prover switch. Prover Leads are not polarity sensitive.

NOTE: If burner safety control goes out on lockout, the Inducer will continue to run as long as a call for heat is present.

Alarm

A

Violet

0.3 A, AC

OIL VALVE

R

A

Blue

Orange

F

F

White

T

Black

Red/White

T

115 VAC

BURNER MOTOR

IGNITION TRANS

500 VA

10 FLA / 60 LRA

Line Voltage Thermostat

60 Hz

SUPPLY

J2

UNI

V

E

R

S

A

L

CO

NT
RO

LLE

R

XN

XL

J1

RED JUMPER POSITION MUST BE THE SAME

AS APPLIANCE INTERLOCK VOLTAGE.

IMPORTANT:

115V

DRY

24V

D/N 9183046-3

115 VAC

LEGEND:

CALL
JUMPER

Limit

or Aquastat Control

Low Voltage
Jumper

50/60 Hz

SUPPLY
115 VAC

SPADE TERMINAL IN ELECTRICAL BOX.

GROUND

CRIMP GROUND WIRE TO GROUNDING

IMPORTANT:

1. Disconnect burner motor wire off the Orange on Carlin and connect burner motor terminal Orange of Carlin to #1 on UC1 terminal block.
2. Connect #2 on UC1 terminal block to L2 or N
3. Connect #4 on UC1 terminal block to burner motor wire removed from Orange of Carlin.
4. Make sure RED voltage jumper on UC1 is on 115V.
5. Connect 115 VAC supply voltage to L & N terminals on UC1. Connect the 2 green ground wires in UCRT to supply ground.

Important: Installer must supply overload and disconnect protection.

6. If not previously completed, connect Black, White and Red leads from UCRT to like colors in Rooftop Inducer whip 4x4 weather-

proof junction box. Connect the Green/Yellow ground lead in UCRT to the ground screw in the Rooftop Inducer whip 4x4
weatherproof box. Connect Blue and Yellow leads from UCRT to PSA-1 Fan Prover switch. Prover Leads are not polarity sensitive.

UC1 UNIVERSAL CONTROL CONNECTED WITH A CARLIN 40200, 42230, 48245, 50200, 60200

SERIES OR EQUIVALENT AND A LINE VOLTAGE THERMOSTAT OR AQUASTAT