Tjernlund HSJ, 1, 2 Series with UC1 Universal Control (Version X.02) 8504106 Rev 08/02 User Manual

Page 16

Advertising
background image

15

UC1 UNIVERSAL CONTROL CONNECTED TO A HONEYWELL

R8184 SERIES OR EQUIVALENT PRIMARY CONTROL

50/60 Hz

R

WHITE

ORANGE

BLACK

HONEYWELL

R8184 SERIES

OR EQUIVALENT

L1

IGNITION TRANS

BURNER MOTOR

WHITE

WHITE

SUPPLY
115 VAC

BLACK

UNIVERSAL CONTROLLER

XN

RED JUMPER POSITION MUST BE THE SAME

IMPORTANT:

AS APPLIANCE INTERLOCK VOLTAGE.

J1

XL

J2

115V

DRY

24V

D/N 9183046-2

115 VAC

LEGEND:

CALL
JUMPER

SPADE TERMINAL IN ELECTRICAL BOX.

GROUND

CRIMP GROUND WIRE TO GROUNDING

IMPORTANT:

1. Separate the Black burner motor wire from the Orange wire of R8184 Primary Control.

NOTE: Do not separate the ignition transformer wire from the Orange.

2. Connect Orange wire of R8184 to #1 on UC1 terminal block.
3. Connect #2 on UC1 terminal block to White on R8184.
4. Connect Black of burner motor to #4 on UC1 terminal block.
5. Make sure RED voltage jumper on UC1 is on 115V.
6. Connect 115 VAC supply voltage to L & N terminals on UC1. Crimp Ground wire to grounding spade terminal in UC1.

Important: Installer must supply overload and disconnect protection.

7. If not previously completed, connect ground from UC1 whip to grounding stud in Venter. Connect Black and White leads

from UC1 whip to Venter motor leads. Connect Blue and Yellow leads from UC1 whip to Fan Prover switch terminals in
Venter. Yellow lead should be on switch terminal closest to Venter junction box wall.

UC1 UNIVERSAL CONTROL CONNECTED WITH A CARLIN 40200, 42230, 48245, 50200, 60200

SERIES OR EQUIVALENT AND A LINE VOLTAGE THERMOSTAT OR AQUASTAT

Alarm

A

Violet

0.3 A, AC

OIL VALVE

R

A

Blue

Orange

F

F

White

T

Black

Red/White

T

115 VAC

BURNER MOTOR

IGNITION TRANS

500 VA

10 FLA / 60 LRA

Line Voltage Thermostat

60 Hz

SUPPLY

J2

UNIVERSAL CONTROLLER

XN

XL

J1

RED JUMPER POSITION MUST BE THE SAME

AS APPLIANCE INTERLOCK VOLTAGE.

IMPORTANT:

115V

DRY

24V

D/N 9183046-3

115 VAC

LEGEND:

CALL
JUMPER

Limit

or Aquastat Control

Low Voltage
Jumper

50/60 Hz

SUPPLY
115 VAC

SPADE TERMINAL IN ELECTRICAL BOX.

GROUND

CRIMP GROUND WIRE TO GROUNDING

IMPORTANT:

1. Disconnect burner motor wire off the Orange on Carlin.
2. Connect burner motor terminal Orange of Carlin to #1 on UC1 terminal block.
3. Connect #2 on UC1 terminal block to L2 or N
4. Connect #4 on UC1 terminal block to burner motor wire removed from Orange of Carlin.
5. Make sure RED voltage jumper on UC1 is on 115V.
6. Connect 115 VAC supply voltage to L & N terminals on UC1. Crimp Ground wire to grounding spade terminal in UC1.

Important: Installer must supply overload and disconnect protection.

7. If not previously completed, connect ground from UC1 whip to grounding stud in Venter. Connect Black and White leads

from UC1 whip to Venter motor leads. Connect Blue and Yellow leads from UC1 whip to Fan Prover switch terminals in
Venter. Yellow lead should be on switch terminal closest to Venter junction box wall.