Tjernlund VP-2, VP-3 (Discontinued) 8504025 Rev A 01/00  User Manual

Page 10

Advertising
background image

4.

IMPORTANT: Wait 4 minutes and push the reset button on linear limit spillage sensing switch.

5. Reconnect the blue lead to the normally open terminal of the gas pressure switch.

6. Light pilot following the heater manufacturer’s instructions. NOTE: Pilot should not have to be relit if using optional Pilot Saver Kit

(P/N 950-2061).

7. Extinguish the pilot with the burner off. Determine after 3 minutes that there is no gas flow to the main burner. If gas flow to the

main burner is detected, replace the water heater gas valve immediately.

VP-2 / VP-3 WATER HEATER VENT PACKAGE LADDER WIRING DIAGRAM

COMBUSTION AIR TEST

WARNING:
The linear limit spillage sensing switch is designed to alert the user to a potentially hazardous condition. It is not designed to, and can-
not replace, regular vent system inspection, appliance servicing and combustion testing.

DO NOT USE IT AS A SUBSTITUTE FOR

PROFESSIONAL APPLIANCE MAINTENANCE.

1. Close all doors and windows of the building. If the appliance is installed in a utility room or closet, close the entrance door. Close fire

place dampers.

2. Turn on clothes dryer. Turn on all exhaust fans, such as range hoods, bathroom exhaust and whole house fans to maximum speeds.

Do not operate a fan used strictly for summer exhausting.