Advertising
background image

3. Following the water heater manufacturer’s instructions, place the appliance in operation, set thermostat for continuous operation.

4. Allow fans and appliance to operate for 5 minutes.

5. Tripping of the Linear LImit spillage sensing switch during the 5 minutes indicates an unsafe operating condition. Turn off fuel supply

to appliance and

DO NOT OPERATE UNTIL UNSAFE VENTING CONDITION IS INVESTIGATED BY PROFESSIONAL

CONTRACTOR OR UTILITY SERVICE PERSONNEL.

6. Return all windows, doors and fans to their previous conditions of use.

7. Sign and date these instructions to verify that the

Sign:

combustion air and safety interlock test have been
completed. These instructions must remain on

Date:

premises.