SAFETY INSPECTION OF A PREVIOUSLY USED OIL APPLIANCE

S

(Perform prior to IN-FORCER installation)

The following procedure is intended as a guide to aid in determining that an appliance is properly installed and is in safe condition for
continuing use. This procedure is based on central furnace and boiler installations and it should be recognized that generalized pro-
cedures cannot anticipate all situations. Accordingly, in some cases deviation from this procedure may be necessary to determine
safe operation of the equipment.

A. This procedure should be performed prior to any attempt at modifications of the appliance or installation of the IN-FORCER.
B. If it is determined there is a condition which could result in unsafe operation, the appliance should be shut off and the owner

advised of the unsafe condition.

The following steps should be followed in making the safety inspection:

1. Visually inspect the venting system and determine there is no blockage or restriction, leakage, corrosion or other deficiencies

which could cause an unsafe condition.

2. Inspect burner and primary control for proper operation.
3. Applicable only to furnaces: Inspect heat exchanger for cracks, openings or excessive corrosion. Check both the limit control

and fan control for proper operation.

4. Applicable only to boilers: Inspect for evidence of water or combustion product leaks. Determine that the water pumps are in

operating condition. Test low water cutoffs, automatic feed controls, pressure and temperature limit controls and relief valves in
accordance with the manufacturer's recommendations to determine that they are in operating order.

SAFETY INSPECTION OF A PREVIOUSLY USED GAS APPLIANCE

(Perform prior to IN-FORCER installation)

The following procedure is intended as a guide to aid in determining that an appliance is properly installed and is in safe condition for
continuing use. This procedure is based on central furnace and boiler installations and it should be recognized that generalized pro-
cedures cannot anticipate all situations. Accordingly, in some cases deviation from this procedure may be necessary to determine
safe operation of the equipment.

A. This procedure should be performed prior to any attempt at modifications of the appliance or installation of the IN-FORCER.

B. If it is determined there is a condition which could result in unsafe operation, the appliance should be shut off and the owner

advised of the unsafe condition.

The following steps should be followed in making the safety inspection:

1. Conduct a gas leakage test of the appliance piping and control system downstream of the shutoff valve in the supply line to the

appliance.

2. Visually inspect the venting system and determine there is no blockage or restriction, leakage, corrosion and other deficiencies

which could cause an unsafe condition.

3. Shut off all gas to the appliance(s).
4. Inspect burners and crossovers for blockage and corrosion.
5. Applicable only to furnaces: Inspect heat exchanger for cracks, openings or excessive corrosion. Check both the limit control and

fan control for proper operation.

6. Applicable only to boilers: Inspect for evidence of water or combustion product leaks. Determine that the water pumps are in

operating condition. Test low water cutoffs, automatic feed controls, pressure and temperature limit controls and relief valves in
accordance with the manufacturer's recommendations to determine that they are in operating order.
* Excerpts from the National Fuel Gas Code (ANSI Z223.1/NFPA #54), Appendix H.