ELECTRICAL

All wiring from the IN-FORCER to the appliance must be appropriate Class 1 wiring as follows: installed in rigid metal conduit, inter-
mediate conduit, rigid non-metallic conduit, electrical metallic tubing, Type MI Cable, Type MC Cable or be otherwise suitably protect-
ed from physical damage.

The IN-FORCER has a high temperature limit switch to deactivate the system in the event of a mechanical room fire. It also has a fan
proving switch to prove operation prior to burner ignition.

8

IN-FORCER WIRED WITH FAN PROVER AND MOTOR ISOLATION RELAYS

IN-FORCER INTERNAL WIRING SCHEMATIC

ACCESSORY RELAYS FOR ISOLATION

24/115 Volt 1/2 H.P. Relay

950-1040

24/115 Volt 1 1/2 H.P. Relay

950-1016

115/115 Volt 1/2 H.P. Relay

950-0480

115/115 Volt 1 1/2 H.P. Relay

950-0483