Vintage Cellars 4200 VSi CellarPro User Manual
Page 16

16
Ducted Installations – Rear Duct Kit
1. Ductwork may be attached to the discharge only, or to both the discharge and
return adapters.
2. The unit is capable of operating with 100 equivalent feet of total ductwork, or
50 equivalent feet for both the discharge and return ducting, for the rear and
the front of the cooling unit. Elbows or bends will reduce this length. Use a
duct sizing program to determine the total equivalent feet of a specific duct
routing design, or consult the manufacturer for recommendations.
3. The “High” fan speed setting is recommended for long duct runs and as
ambient temperatures rise.
Ducted Installations – Front Duct Kit
1. Ductwork must be attached to BOTH the intake and exhaust openings,
connecting the cooling unit and the wine cellar.
2. The front duct kit includes two duct hoods. One hood is designed for intake
and will cover the lower portion of the cooling unit. This hood is completely