LPQ SERIES

US Cellar Systems / 3070 Golden Ave, Long Beach, CA 90806 / www.uscellarsystems.com
(562) 513-3017 phone and fax / [email protected]

LPQ Cooling System Typical Installation

• Keep line sets as short as possible.

• Excessive number of turns will cause

refrigerant flow problems. This could
cause early compressor failure. Suction
line accumulators are recommended.
Required if working lower than the
normal 55-65° operating range from
wine cellar.

• Drain line must always flow down hill to

drain or pump

• The system is controlled by a pump down

control system. There is no control wiring
between thermostat and condensing unit

• The line connections at Fan Coil and

Condensing Unit may not be the same as
the required line sizes

• Standard line sets should be 50' or less.

Extended runs may require larger line
sizes and 3oz. oil must be added for
every 10' over 35'.

REFRIGERATION
LINES

CEILING

CONDENSING UNIT

WA

LL

LPQ FAN COIL

DRAIN LINE

LPQ FAN COIL

RACKING

RACKING

CEILING

WA

LL

WA

LL

LEAVE 2"ON EACH SIDE

AND 6" BELOW FOR

SERVICE INTERIOR

ACCESS
3" BEHIND FOR AIR

CIRCULATION