Wine-Mate SSHWC Series User Manual

Page 25

Advertising
background image

- 24 -

Low subcooling
5) High suction pressure and high head pressure
Low superheat and low subcooling
6) High suction pressure and high head pressure
High superheat
7) Low suction pressure and low head pressure
High superheat and low subcooling
8) Low suction pressure and low to normal head pressure
High superheat and high subcooling

9) Low suction pressure and low head pressure
Normal to high superheat and low subcooling
10) Low suction pressure and low head pressure
Low superheat and low subcooling
11) Low suction pressure and low to normal head pressure
High superheat and normal to high subcooling
12) Low suction pressure and normal head pressure
High superheat and normal subcooling
13) Low suction pressure and high head pressure
High superheat and high subcooling

14) Low suction pressure and high head pressure
High superheat and high subcooling
15) low to normal suction pressure and high head pressure
Normal to high superheat and high subcooling


5) Water restricted or bad water

regulator, dirty condenser

6) High cellar temperature, high

evaporator load

7) Undercharge

8)

Liquid line restricted after
receiver, solenoid valve
restricted

9) Suction line restricted

10)

Air restricted at evaporator,
evaporator iced

11) Evaporator restricted

12) Expansion valve restricted

13) Both evaporator and condenser

restricted; liquid and suction
lines connected wrong

14)

Liquid line restricted before
receiver

15) Condenser restricted


12. Condensing Unit Troubleshooting

Unit not running

1) Incorrect power supply
2) Incorrect or loose wirings
3) Failed

components

4) Low pressure control shutting down the

system

5) High pressure control shutting down the

system

1) Check for proper voltage
2) Check all wirings and connections
3) Check start relay, start capacitor,

overload protector, compressor.

4) Check for system restriction or low

refrigerant

5) Check the condenser water flow