*Field-supplied.

NOTES:
1. Factory wiring is in accordance with NEC. Field modifications or

additions must be in compliance with all applicable codes.

2. Wiring for field power supply must be rated 75 C minimum. Use

copper, copper-clad aluminum, or aluminum conductors. Maxi-
mum incoming wire size for each terminal block is 500 kcmil.

3. Terminal blocks TB3, TB4, TBX1, and TBX2 are for external field

control connections. Control connections are to be Class 1 wiring.

4. Field-supplied components (IFC, LLS-A1, A2, B1, and B2) must

have a maximum sealed coil rating of 30 va each (0.25 amp at
120 vac, 0.13 amp at 230 vac). AHMS IFC-AUX contact must have
minimum pilot duty rating of 375 va each (3.1 amps at 120 vac,
1.6 amps at 230 vac).

5. Replacement of factory wires must be with type 105 C wire or its

equivalent.

6. Field-supplied liquid line solenoid valves installed at the evapora-

tor are required on all units.

7. Control has 35 va of power available for field-installed accessories.

LEGEND

AHMS — Air Handler Motor Starter
AUX

Auxiliary

C

Compressor Contactor

FU

Fuse

GND

Equipment Ground

IFC

Indoor Fan Control

kcmil

Thousand Circular Mils

LLS

Liquid Line Solenoid

NEC

National Electrical Code

(U.S.A. Standard)

SDR

Solenoid Drop Relay

TB

Terminal Block

TBX

Terminal Block for

Variable Air Volume
Units

TM

Timer Motor

TR

Timer Relay

TRAN — Transformer
U

Unloader Solenoid

Factory Wiring
Field Wiring

Fig. 27 — Field Wiring, Single ModuPanel™ Control, Unit 38AH104

35