Carrier 38HDF018-036 User Manual

Page 8

Advertising
background image

8

Table 3 — 38HDR Electrical Data

LEGEND

*Permissible limits of the voltage range at which unit will operate

satisfactorily.

NOTES:
1. Control circuit is 24 v on all units and requires an external power

source.

2. All motors and compressors contain internal overload protection.
3. In compliance with NEC (U.S.A. Standard) requirements for mul-

timotor and combination load equipment (refer to NEC Articles
430 and 440), the overcurrent protective device for the unit shall
be fuse or HACR breaker.

4. Motor RLA values are established in accordance with UL (Under-

writers’ Laboratories) Standard 465 (U.S.A. Standard).

5. 38HDF,HDR018-030 units are only available in single-phase

voltage.

6. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percentage of voltage imbalance:

EXAMPLE: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

Determine maximum deviation from average voltage:
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percentage of voltage imbalance:

This amount of phase imbalance is satisfactory as it is below the
maximum allowable of 2%

38HDR

UNIT SIZE

V-PH-Hz

VOLTAGE RANGE*

COMPRESSOR

OUTDOOR FAN MOTOR

MIN CKT

AMPS

FUSE/HACR

BKR AMPS

Min

Max

RLA

LRA

FLA

NEC Hp

kW Out

018

208/230-1-60

187

253

10.0

48.0

0.80

0.125

0.09

13.3

20

024

208/230-1-60

187

253

14.3

58.3

0.80

0.125

0.09

18.7

30

030

208/230-1-60

187

253

15.7

64.0

1.45

0.25

0.19

21.1

35

036

208/230-1-60

187

253

15.7

77.0

1.45

0.25

0.19

21.1

35

208/230-3-60

187

253

10.4

88.0

1.45

0.25

0.19

14.5

20

460-3-60

414

506

6.3

38.0

0.80

0.25

0.19

8.7

15

048

208/230-1-60

187

253

24.3

117.0

1.45

0.25

0.19

31.8

55

208/230-3-60

187

253

15.6

83.1

1.45

0.25

0.19

21.0

35

460-3-60

414

506

6.9

41.0

0.80

0.25

0.19

9.4

15

060

208/230-1-60

187

253

29.4

134.0

1.45

0.25

0.19

38.2

65

208/230-3-60

187

253

17.8

110.0

1.45

0.25

0.19

23.7

40

460-3-60

414

506

8.6

52.0

0.80

0.25

0.19

11.6

20

FLA

Full Load Amps

HACR — Heating, Air Conditioning, Refrigeration
LRA

Locked Rotor Amps

NEC

National Electrical Code

RLA

Rated Load Amps (Compressor)

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

=

457

% Voltage Imbalance = 100 x

7

457

= 1.53%

IMPORTANT: Contact your local electric utility company immedi-
ately if the supply voltage phase imbalance is more than 2%.