Test/Inspection

Frequency

Comments

Inspect area surrounding heating plant

Daily

Keep area clean and free of clutter

Inspect gas supply system for leaks

Daily

Use visual and electronic leak detection

Inspect appliance & piping for water leaks

Daily

Keep burner and controls dry at all times

Inspect gauges, indicators, monitors

Daily

Note condition. Replace defective parts

Check temperature and pressure levels

Daily

Compare to manufacturer’s specifi cations

Make visual inspection of fl ame

Daily

Look for changes in shape, size, and color.

Monitor burner start-up

Daily

Verify prompt ignition and fl ame stability.

Monitor stack temperature

Daily

Compare to start-up and trend level.

Test low water cutoff and alarm

Daily

Follow control manufacturer’s instructions & procedures
in ASME Boiler & pressure vessel Code, Section VI -
Recommended rules for care and operation of heating
boilers.

Calculate fuel gas input fi ring rate

Weekly

Compare to appliance manufacturer’s Specifi cations

Check fl

ame safeguard sequence of

operation.

Weekly

Follow control manufacturer’s instructions

Flame failure response & lockout timing.

Weekly

Follow control manufacturer’s instructions

Flame sensor signal level (if meter is hard-
wired)

Weekly

Compare to control manufacturer’s specifi cations

Main fuel gas valves

Weekly

Open high limit and verify cutoff operation

Inspect exhaust vent system for blockage

Weekly

Remove any restrictions

Inpect combustion air supply

Monthly

Remove any restrictions

Check high and low gas pressure interlocks Monthly

Follow control manufacturer’s instructions

Check safety valves

As needed

Follow control manufacturer’s instructions & procedures
in ASME Boiler & Pressure Vessel Code, Section VI -
Recommended Rules for Care and Operation of Heating
Boilers.

Table 5 - Periodic Inspection Sheet

Inspect Heating System
Regularly

Lack of regular inspections and inadequate

maintenance could lead to equipment malfunction

and result in asphyxiation, explosion or fi re.

(Always follow the appliance manufacturer’s
recommended service instructions, when available.)
The following checklist is intended to be used as a
minimum reference guide only and does not supersede
or replace the heating appliance manufacturer’s
recommended service and maintenance instructions or
any code requirements.
Consult the installation and service instructions provided
by the individual control or component manufacturer
and carefully follow their directions.
Maintenance and testing may be required more
frequently due to dusty or severe operating conditions.
If unusual or questionable performance is observed,
shut the system down and contact your qualifi ed service
agency immediately.