Configuration level items, Parameter level items, User level items – Beckett RWF40 Hints Manual User Manual
Page 14: 2 your record of values

13/16 CC1B-Hints-en
Preliminary
04.02.2003 HVAC Products
3. Notes
3.2 Your record of values
RWF40
Setpoint
Your
Man. Ref.
Display
Setting
Configuration level items
( Sec 6.4 )
Range
Factory
Sec 8.1
C111
Analog input 1, 2 and 3;D2 setpoint changeover / shift
N /A
9030
Sec 8.1 / 8.2
C112
Limit comparator; controller type; setpoint 1; locking
N /A
0010
Sec 8.1
C113
Unit address; decimal place / unit, signal for out-of-range
N /A
0110
Sec 8.3.1
SCL
SC
ale
L
ow, analog input 1, measured value range
-1999 to +9999
0
Sec 8.3.2
SCH
SC
ale
H
igh, analog input 1, measured value range
-1999 to +9999
100
Sec 8.3.3
SCL2
SC
ale
L
ow, analog input
2
, measured value range
-1999 to +9999
0
Sec 8.3.4
SCH2
SC
ale
H
igh, analog input
2
, measured value range
-1999 to +9999
100
Sec 8.3.5
SPL
S
et
P
oint
L
ow limit
-1999 to +9999
0
Sec 8.3.6
SPH
S
et
P
oint
H
igh limit
-1999 to +9999
100
Sec 8.3.7
OFF1
OFF
set analog input
1
, Actual value correction
-1999 to +9999
0
Sec 8.3.8
OFF2
OFF
set analog input
2
, Actual value correction
-1999 to +9999
0
Sec 8.3.9
OFF3
OFF
set analog input
3
, Actual value correction
-1999 to +9999
0
Sec 8.3.10
dF1
d
igital
F
ilter, analog input
1,
2
nd
order, in seconds
0 to 100
1
Setpoint
Your
Display
Setting
Configuration level items
, Modbus option (only RWF40.0X2B97)
( Sec 6.4 )
Range
Factory
Sec 8.3.11
dF3
Filter time constant,
d
igital
F
ilter, analog input
3
weather-dependent setpoint shift
0 to 1440
1278
Sec 8.3.12
oLLo
W
o
rking range,
L
imit
Lo
wer
-1999 to +9999
-1999
Sec 8.3.13
oLHi
W
o
rking range,
L
imit
Hi
gh
-1999 to +9999
9999
Sec 8.3.14
Dtt
Bus wa
t
ch
D
og
t
imer (in seconds)
0 to 7200
30
Setpoint
Your
Display
Setting
Parameter level items
( Sec 6.3 )
Range
Factory
Sec 7 / 8.2
AL
A
larm value for K6
L
imit comparator (alarm programmable relay)
-1999 to +9999
0
Sec 7 / 8.2
HYSt
Hyst
eresis, (switching differential) for K6 limit comparator
0 to 999.9
1
Sec 7 / 8.2
Pb.1
P
roportional
b
and
1
(affects P-response of controller)
0.1 to 999.9
10
Sec 7 / 8.2
dt
d
erivative
t
ime (in seconds) (affects D-response of controller)
0 to 9999
80
Sec 7 / 8.2
rt
Integ
r
al action
t
ime (in seconds) , (affects I-response of controller)
0 to 9999
350
Sec 7 / 8.2
db
*
d
ead
b
and, contact spacing, * visible when C112 is xxx0, 3-pos modulating
0 to 999.9
1
Sec 7 / 8.2
tt
*
Ac
t
uator running
t
ime (in seconds) , * visible when C112 is xxx0, 3-pos modulating
10 to 3000
15
Sec 7 / 5.51
HYS1
Switch-on threshold,
HYS
teresis
1
, 2-stage burner
0 to -199.9
-5
Sec 7 / 5.2
HYS2
Switch-off threshold,
HYS
teresis
2
, 2-stage burner
0 to HYS3
3
Sec 7 / 5.2
HYS3
Switch-off threshold,
HYS
teresis
3
, upper
0 to 999.9
5
Sec 7 / 5.6
q
Response threshold (
Q
)
0 to 999.9
0
Sec 7 / 5.51
H
H
eating curve slope
0 to 4
1
Sec 7 / 5.5
P
P
arallel displacement (weather dependent setpoint shift)
-90 to +90
0
Setpoint
Your
Display
Setting
User level items
( Sec 6.2.1 )
Range
Factory
Sec 6.2.1
SP1
S
et
P
oint
1
SPL to SPH
0
Sec 6.2.1
SP2
S
et
P
oint
2
, digital input 2, D2=0
SPL to SPH
0
Sec 6.2.1
dSP
d
igital
S
et
P
oint shift, digital input 2, D2=1
SPL to SPH
0
Sec 11.1.3
tA
t
emperature,
A
mbient (outside) analog input 3, visible when C111 is xx1x, xx2x, xx3x
--
Sec 11.1.2
SP.E
S
et
P
oint
E
xternal, predefinition, analog input 2, visible when C111 is xx1x, xx2x, xx3x
SPL to SPH
--