2. Hints

2.2 How to configure your RWF40



Shown at the right is the basic display.

The current configuration of your specific

controller will determine which levels you will be allowed
to access.

C112 must be xxx0 to access the configuration level.



The C112 locking code can only be adjusted by the manufacturer.



To reach the configuration level, you start from
the basic display, (shown above), skip past the user
level, and go first, to the parameter level, and
then, finally, to the configuration level.

Press

and hold for 3 seconds, and then release it.



You are now at the parameter level.



From the parameter level you may now advance
to the configuration level,
by pressing

again, holding, for 3 seconds,

and then releasing it.

The actual value display, (

9030

)

shows the current configuration value.

The setpoint display, (

C111

)

shows the configuration item you are adjusting.


Configuration level items summary :

C111

Analog input 1

sensors (14 types), standard signal

Analog input 2

none, external SP, analog SP Shift

Analog input 3

none, outdoor sensors …

D2 function

none, SP chg/over, SP binary shift

C112

Limit comparator

none, input 1,2,3 …

Controller type

3-position, modulating 0-20mA, …

Setpoint SP1

via buttons, with outside sensor

Locking

none, configuration, parameters, buttons

C113

Unit

address

Unit address

0-9
0-9

Decimal - Units

º C or º F and decimals

Signal out-of-range

limit comparator OFF/ON

SCL SC

ale

L

ow Analog input 1

SCH SC

ale

H

igh Analog input 1

SCL2 SC

ale

L

ow Analog input

2

SCH SC

ale

H

igh Analog input

2

SPL S

et

P

oint,

L

ower

SPH S

et

P

oint,

H

igher

OFF1

Actual value correction,

OFF

set, Analog input

1

OFF2

Actual value correction,

OFF

set, Analog input

2

OFF2

Actual value correction,

OFF

set, Analog input

3

Df1 D

igital

f

ilter time constant for Analog input

1

Example Re-configure (adjust) the value for C111

If no keys are pressed for 30 seconds, at anytime, the controller will

automatically return to the basic display.


The current value of C111, (

9030

)

is shown in the actual value display.

The current configuration item (

C111

)

is shown in the setpoint display.

The display is steady, (not flashing) and by default,
the 4

th

, (rightmost) digit is the one you may now

adjust.


You can select the digit you want to adjust,
by pressing

once and releasing it.


The 3

rd

digit is now flashing,

indicating that it is now, the adjustable digit.

(Each time you press and release

you cycle,

thru each digit, right-to-left and back again)





To change the value of the flashing digit,
press

and release it.


Each time you press

and release, you cycle

up thru the allowable values, and back again.






Once you have the desired value displayed
and flashing,
you may accept it by pressing

once

and releasing it.

All four upper digits will flash once.

The controller displays the new configuration
values, in 4 steady digits.




Your options at this point are:

Press

and release

,

to immediately return to the basic display.

or
press

and release it, to advance to C112,

press

again and release it, to advance to C113,

press

and release it, to advance to SCL,

… after the last configuration item Df1,


press

and release it, to advance to AL, (the 1

st

parameter),

… after the last parameter item P,


press

and release it, to advance to SP1, (the 1

st

user item),

… after the last user item it cycles back to the 1

st

user item.


Or simply wait 30 seconds and the controller will automatically
return to the basic display.