2. Hints

2.5 How to display the software version and
units

RWF40 user manual Section 6.2 .5



Shown at the right is the basic display.

The current configuration of your specific

controller will determine which levels you will
be allowed to access.

A C112 of xxx3 will prevent use of the keys.

The C112 locking code can only be adjusted by the manufacturer.



You can display the software version, and units, of your controller,at any
time, by pressing the

at the same time,and holding them…


You will see one, of the three displays shown below.
















The software version of your controller, (Version

102

in this example.) is

shown in the actual value display.

The current units configuration (

ºC

,

ºF

, or

%

) is shown in the setpoint

display.

The display will return, to the where it was, if you release the keys at

the same time, if not, you will return back to the basic display.

Configure Codes \ Units summary:

ºC will be displayed if your controller is configured with:

C111

0xxx .. dxxx

Analog input 1

Sensor (Pt100, Ni100, .. )

C113

xx0x No

decimals

ºC

C113

xx1x One

decimal

ºC

ºF will be displayed if your controller is configured with
C111

0xxx .. dxxx

Analog input 1

Sensor (Pt100, Ni100, .. )

C113

xx2x

No decimals

ºF

C113

xx3x

One decimal

ºF

% w ill be displayed if your controller is configured with:
C111

Exxx .. Hxxx

Analog input 1

Standard input (4-20mA, .. )

C113

xx0x .. xx3x

Doesn’t matter
















2.6 Manual operation

RWF40 user manual Section 6.2 .2 and 6.2.3.



Shown at the right is the basic display.

The current configuration of your specific

controller will determine which levels you will
be allowed to access.

A C112 of xxx3 will prevent use of the keys.



The C112 locking code can only be adjusted by the manufacturer.





Manual operation can only be performed

when the thermostat function is active
and burner is released to modulation.

The

green

burner LED must be on,

relay 1 is energized, and the contact,
Q13 N.O. - Q14 Com, is closed.

If at any time the burner LED turns off, the
controller will exit the manual operation function.