Controller Functions

975-0004-01-02 Rev D

11

or automatic reconnect when the

C-Series

is used as a load

controller. Do not use this decal if using the

C-Series

controller

as a PV Charge Controller or Diversion Controller.

Low Voltage Disconnect

When configured as a load controller, the

C-Series controller

will disconnect the load from the batteries when it reaches the
LVD setting. There will be a 6-minute delay after the voltage
drops below the Low Voltage Disconnect (LVD) setting
before the controller actually disconnects the load.

Low Voltage Reconnect

It can also provide automatic reconnection of the loads at the
LVR (Low Voltage Reconnect) setting. Reconnection of the
load is allowed once the battery voltage has exceeded the
Low Voltage Reconnect (LVR) setting.

Loads are either automatically or manually reconnected when
battery voltage exceeds the Low Voltage Reconnect (LVR)
setting for 6 minutes.

See

“Operating Mode Jumper” on page 20

for instructions on

enabling this mode.

Figure 1-5 Load Controller

Important:

When using the DC Load Control mode:

• Do not temperature-compensate these settings.
• Do not install the optional battery temperature
compensation sensor.