Installation Requirements

The fireplace must meet the minimum dimensions listed below. (Fig. 1) Do not install the logset if the fireplace does
not meet these minimums.

Pressure Test Points

Copreci Valve: 1/8” N.P.T. plugged tapping is provided
on the outlet side of the gas control for a test manifold
pressure.
SIT Valve: Inlet and manifold taps are provided on the
right side of the valve.

Proposition 65 Warning: Fuels used in gas, wood-
burning or oil fired appliances, and the products of
combustion of such fuels, contain chemicals known
to the State of California to cause cancer, birth de-
fects and other reproductive harm.
California Health & Safety Code Sec. 25249.6

FD370-2

Fireplace

dimensions/vl18

3/25/99

A

B

D

C

A. Front Width B. Rear Width C. Depth D. Height

FD370-2

Fig. 1 Minimum fireplace dimensions.

High Elevations

Input ratings are shown in BTU per hour and are
certified without deration from elevations up to
4,500 feet (1,370 m) above sea level.
Nuisance outages may occur at altitudes above
4,500 feet (1,370 m) if dirt, dust, lint and/or cob-
webs are allowed to accumulate on burner and/or
ODS pilot. Monthly inspection and cleaning is
recommended for altitudes above 4,500 feet
(1,370 m)
For elevations above 4,500 feet (1,370m) in USA,
installations must be in accordance with the
current ANSI Z223.1/NFPA 54 and/or local codes
having jurisdiction.
In Canada, please consult provincial and/or local
authorities having jurisdiction for installations at
elevations above 4,500 feet (1,370 m)

Odor During Operation

Neither natural gas nor propane gas give off an odor
when burned. The nature of a vent free combustion
system, however, is such that odors may occasionally
be produced during heater operation when impurities
exist in the immediate area. Cleaning solutions, paint,
solvents, cigarette smoke, candles, adhesives, new car-
pet or textiles, etc., all can create fumes. These fumes
may mix with combustion air and can create odor. Such
odors will disappear over time, however, the condition
can be alleviated by opening a window or otherwise
providing additional ventilation to the area.

Min. Fireplace Dimensions

Inlet Supply

Min.

Max.

Air

Logset

Gas

Front

Rear Overall Overall Pressure (w.c.) Manifold Input

Input

Shutter

Width Width Depth Height

Min. Max.

Pressure BTU/hr

BTU/hr

Setting

18” VL18

21”

16¹⁄₂”

13¹⁄₂”

17”

5.0 10.5

3.5

15,000

24,000 .188” Open

21” VL21

Natural

21”

18¹⁄₂”

13¹⁄₂”

17”

5.0 10.5

3.5

18,000

32,000 .250” Open

24” VL24

25”

18¹⁄₂”

13¹⁄₂”

17”

5.0 10.5

3.5

18,000

35,000 .375” Open

Cop. SIT

18” VL18LP

21”

16¹⁄₂”

13¹⁄₂”

17”

11.0 14.0

8.5 10.0 15,000 24,000 Full Open

21” VL21LP Propane 21”

18¹⁄₂”

13¹⁄₂”

17”

11.0 14.0

8.5 10.0 18,000 32,000 Full Open

24” VL24LP

25”

18¹⁄₂”

13¹⁄₂”

17”

11.0 14.0

8.5 10.0 18,000 35,000 Full Open