Fig. 8 — field wiring schematic – Carrier 30GTN015-035 User Manual

Page 10

Advertising
background image

10

REMOTE

ON-OFF

TB4

Fig. 8 — Field Wiring Schematic

NOTES:

1. Factory wiring is in accordance with the National Electrical Code. Any field mod-

ifications or additions must be in compliance with all applicable codes.

2. Connect separate source of control power from field supplied fused disconnect

to terminal 1 of TB4. Neutral side must be connected to terminal 2. This provides
power for the unit control circuit, cooler heater and compressor crankcase
heater.

3. All field interlock contacts must have minimum rating of 360 va pilot duty plus

capacity required for field-installed equipment.

4. For internal unit wiring reference wiring book or unit wiring label diagram.
5. For GCS accessory, remove jumper wire between terminals 5 and 8 on terminal

block TB2.

6. For part wind start accessory, remove gray jumper wire between C-A1-C1 and

C-A1A-C1. Time delay relay shown in suggested mounting position.

7. Voltage requirements:

MAIN POWER

CONTROL POWER

208/230-3-60

115-1-60

460-3-60

115-1-60

575-3-60

115-1-60

380-3-60

220-1-60

380/415-3-50

230-1-50

LEGEND

C

Compressor Contactor

CB

Circuit Breaker

CCN

Carrier Comfort Network

CWFS —

Chilled Water Flow Switch

CWP

Chilled Water Pump

CWPI

Chilled Water Pump Interlock

FC

Fan Contactor

GCS

Ground Current Sensor

LEN

Local Equipment Network

MBB

Main Base Board

NEC

National Electrical Code
(U.S.A. Standard)

TB

Terminal Block

TDR

Time Delay Relay

TRAN

Transformer
Field Power Wiring

Field Control Power Wiring

Field Control Wiring

Factory-Installed Wiring

Field-Installed Device