5| Electrical connection

5.6 Electronic trigger unit INT69 G

5.7 Connection of the trigger unit INT69 G

The compressor motor is fitted with cold conductor temperature sensors (PTC) connected to the
electronic trigger unit INT69 G in the terminal box. In case of excess temperature in the motor
winding, the INT 69 G deactivates the motor contactor. Once cooled, it can be restarted only if the
electronic lock of the output relay (terminals B1+B2) is released by interrupting the supply voltage.
The hot gas side of the compressor can also be protected against overtemperature using thermal
protection thermostats (accessory)

.

The unit trips when an overload or inadmissible operating conditions occur. Find and remedy
the cause.

PTC1

PTC2

N

L

B1 B2 12 14 11

PTC

Motor Protection INT69 G

Terminal box

Abb. 23

supply

Lock out

INFO

The relay switching output is executed as a floating changeover
contact. This electrical circuit operates according to the quiescent
current principle, i.e. the relay drops into a the idle position and
deactivates the motor contactor even in case of a sensor break or
open circuit.

INFO

Connect the trigger unit INT69 G in accordance with the circuit dia-
gram. Protect the trigger unit with a delayed-action fuse (F) of max.
4 A. In order to guarantee the protection function, install the trigger
unit as the first element in the control power circuit.

ATTENTION
PTC cable on the trigger unit
INT69 G and terminals PTC 1 and
PTC 2 on the compressor termi-
nal board must not come into
contact with mains voltage.
This would destroy the trigger
unit INT69 G and PTC sensors.