3 | areas of application – GEA Bock HG88e User Manual

Page 8

Advertising
background image

8

D
GB
F
E
I
Ru

96260-11.2014-DGbFEIRu

3| Areas of application

The compressors are filled at the factory with the following oil type:

- for R134a, R404A/R507, R407C, R407F

FUCHS Reniso Triton SE 55

- for R22

FUCHS Reniso SP 46

Compressors with ester oil charge (FUCHS Reniso Triton SE 55) are marked with an X in the type
designation (e.g. HG

X88e/3235-4).

3.1 Refrigerants
• HFKW / HFC:

R134a, R404A/R507, R407C, R407F

• (H)FCKW / (H)CFC:

R22

3.2 Oil charge

3.3 Limits of application

ATTENTION Compressor operation is possible within the operating limits

shown in the diagrams. Please note the significance
of the shaded areas. Thresholds should not be selected as
design or continuous operation points.
- Permissible ambient temperature (-20°C) - (+60°C)
- Max. permissible discharge end temperature 140°C.
- Max. permissible switching frequency 12x /h.
- A minimum running time of 3 min. steady-state condition
(continuous operation) must be achieved.
For operation with supplementary cooling:
- Use only oils with high thermal stability.
- Avoid continuous operation near the threshold.
- Additional fans (accessories) can be used for additional cooling.
For operation with capacity regulator:
- The suction gas superheat temperature may need to be reduced

or set individually when operating near to the threshold.

- The limits of application are reduced.
For operation with frequency converter:
- The maximum current and power consumption must not be

exceeded. In the case of operation above the mains frequency, the
application limit can therefore be limited.

When operating in the vacuum range, there is a danger of air
entering on the suction side. This can cause chemical reactions,
a pressure rise in the condenser and an elevated compressed-gas
temperature. Prevent the ingress of air at all costs!

INFO

For refilling, we recommend the above oil types.
Alternatives: see lubricants table, Chapter 7.4.

ATTENTION The oil level must be in the

visible part of the sight
glass; damage to the com-
pressor is possible if over-
filled or underfilled!

max.

min.

3,0 Ltr.

oil level

Fig. 3

~

~