Page 32

Advertising
background image

2-5

Temporary Suspension of Safety Function

2-8

GL-RHG-M-NO2-E

Fu
nct
ion
s and

Feat

ures

2

Devices used for muting function

Muting device

•

The muting device output must be N.O. (normally open).

•

A PNP output muting device is required when using the PNP output type cable and an NPN output mut-
ing device is required when using the NPN output type cable. The muting device must be capable of 2 to
3 mA current.

•

Do not use one muting device with multiple outputs in place of two or more muting devices. (Only one
output per one muting device must be used.)

•

If the muting device has a timer function that can adjust the output timing, do not use that function.

Muting lamp

When using the muting lamp, it must meet the following conditions.

For an incandescent lamp : rated 24 V DC, 1 to 5.5 W
For an LED indicator

: rated current consumption must be 10 to 230 mA.

Detailed operation

Conditions for initiation of muting

Muted condition is initiated if all of the following conditions are met:
•

Muting input 2 turns ON within 0.04 to 3 seconds after muting input 1 turns ON

•

GL-RHG detects no interruption in the protective zone

•

OSSD is in the ON state and remains for 0.5 seconds or more.

Conditions for termination of muting

Muted condition is terminated if one of the following conditions is met.
•

Either of the muting inputs goes to the OFF state for at least 5 ms.

•

Light curtain goes to an error condition

•

Wait input goes to ON state

•

The power supply is interrupted or restored.

•

Maximum muting period of approx. 5 minutes has been passed.

Reference

When the GL-RHG is interrupted, the GL-RHG cannot go to the muted condition. In this case, you
can apply override function to suspend the safety functions temporarily.

"Override function" (page

2-20)