3.3 Typical RU Housing Details

A typical Recirculation Unit Model RU500 is shown.

Final filter track

2" After-filter track

Second stage HD
cassette positioning
and support track,
sealing face

Typical insulated
double wall panel

Fan section

Extruded

aluminum track

First stage HD
cassette positioning
and support track,
sealing face

2" Prefilter track

Outlet air grille

Door hinge

Door latch

Insulated double
wall access doors

Pressure gauges

Fan control

Filter side-seal gaskets

Track support

Inlet air grille

The RU is uniquely designed to accommodate and securely seal AAF’s
gas-phase chemical filter cassettes. Each housing incorporates AAF’s
patent-pending filter sealing system to ensure that the contaminated air
passes through the filter and does not by-pass around the filters. Typical
details of the tracks are shown in these illustrations. In some instances,
depending on the equipment supplied and the filters required, minor
track details may differ from those shown.

2" Prefilter track

Galvanized steel
(or similar) formed track

2" After-filter and final filter track. The final
filter track shown is designed to accept a
typical 1" nominal header-style filter.

Hollow core gasket

2" After-filter track

Final filter track

Cassette support track, sealing face

Hollow core face sealing gasket

Plastic strips provide low
friction cassette bearing surface

Track support hardware

Track support beam

Extruded aluminum track

Track connection detail at support beam. This detail shows AAF’s “quick release” track
installation method. Accurately located support post holes ensure high tolerance track
spacing. Note that the track connection is completely isolated from the filter sealing
surface and cannot interfere with filter installation.