Figure 2. Typical placement for SAAFShield units.

3.0 Placement of SAAFShield Monitors

When determining the reactivity of a room or space within a building,

the SAAFShield should be placed in a location representative of the air

that contacts the electronics or materials being protected. If the

protected items are spread out within the space, then an approach,

similar to a thermostat should be used. If the protected items are

concentrated in one area inside the space, then a location as close as

possible to them is preferred.
When determining the condition downstream of a gas-phase filter or

scrubber to evaluate media performance and life, the SAAFShield

should be placed after the final particulate filter. This will protect it from

the majority of particulates and allow it to monitor the condition of the

outlet air. When the rate of corrosion begins increasing beyond what is

normal, it is time to change the media or filter.

4.0 Connecting to SAAFShield Detecting Unit

The SAAFShield Detecting Unit and Communications Module come

equipped with 26-pin ribbon cable connectors. To connect the CM to

the DU, first remove the CM cover and locate the ribbon cable connec-

tor at the top of the CM circuit board. (Figure 3)

SAAF™ Side

Access Housing

SAAFShield

®

Detect-

ing Unit

SAAFShield

®

Reading Unit

(for periodic data

SAAFShield

®

Communications Module

(for continuous

data transmission)

Computer Room Air

Conditioning Unit

(CRAC)

SAAF™

Recirculation Unit

SAAF™ Deep

Bed Scrubber

SAAF™

Pressurization and

Recirculation Unit