8.0 Data Input and Output

The SAAFShield Detecting Unit control logic interface block interprets

the 4-20 mA signal originating in the SAAFShield Communications

Module and produces a set of data consisting of each piece of data

collected by the SAAFShield detecting unit. The block also has some

failure detection capabilities. If a failure is detected the Fail bit is set

and a fail code is populated.

Block Diagram

SAAFShield

Communications

Module

FAL
CumCu
CumAg
IncCu
IncAg
RH
Temp
Error

In

Qui

Rst

Inputs

Parameter Name Type

Description

In

DINT

Physical IO Tag

Qui

Boolean Signal Quality

Rst

Boolean Initialize output to starting values

Notes:

The range and unit of measure for all metal readings is 0 – 4000 angstroms.

• Relative Humidity is measured 0 – 100%.

• Temperature is measured -50 – 150º C

Pulse Codes

Variable

Number

Pulse Level

Length

of Pulses

(raw value)

of Time

Start Signal

1

6.28 mA or 16486

3 seconds

Inter-data Pulse 2

8.58 mA or 22486

1 second each

Data Transfer

1

N/A

5 seconds

Details

Parameter Name Type

Description

FAL

Boolean True if QUI is False

CumCu

DINT

Cumulative Copper reading in angstroms

CumAg

DINT

Cumulative Silver reading in angstroms

IncCu

DINT

Incremental Copper reading in angstroms

IncAg

DINT

Incremental Silver reading in angstroms

RH

Real

Relative Humidity reading

temp

Real

temperature reading

error

Real

error Code

Cycle

every 15 minutes the SAAFShield Communications Module sends data

to the analog input (SigIn). It sends the start signal for 3 seconds, waits

2 seconds, and then begins data transmission. each measurement

is transmitted for 5 seconds. there is a two second wait followed by

two inter-data pulses. Then the next measurement sequence is

transmitted. The chart below (Figure 6) shows an example sequence.

Note that all data transmitted is set high. When the Communications

Module has sent all pieces of data, it waits for 15 minutes before

beginning the cycle.

Steps

1. Send one 6.28 mA pulses of 3 seconds.
2. Wait 2 seconds.
3. Transmit Cumulative copper data in the range of 4-20mA

for 5 seconds.
4. Wait 2 seconds.
5. Send two 8.58 mA pulses of 1 second each with inter-pulse

pause of 1 second (set loop to 4mA during pause)
6. Wait 2 seconds.
7. Transmit Cumulative silver data in the range of 4-20mA

for 5 seconds.
8. Wait 2 seconds.
9. Send two 8.58 mA pulses of 1 second each with inter-pulse

pause of 1 second (set loop to 4mA during pause)
10. Wait 2 seconds.
11. Transmit incremental copper measurement in the range of 4-20mA

for 5 seconds.
12. Wait 2 seconds.
13. Send two 8.58 mA pulses of 1 second each with inter-pulse

pause of 1 second (set loop to 4mA during pause)
14. Wait 2 seconds.
15. Transmit incremental silver measurement in the range of 4-20mA

for 5 seconds.
16. Wait 2 seconds.
17. Send two 8.58 mA pulses of 1 second each with inter-pulse

pause of 1 second (set loop to 4mA during pause)
18. Wait 2 seconds.

Figure 6.