INITIAL START-UP

11. If the required oxygen level from Table 1 is

achieved, proceed to step 18. If the oxygen
level is lower than the required value and
cannot be sufficiently raised using the
differential regulator, proceed to step 12.

12. Close the 1/4” ball valve in the staged

ignition assembly downstream of the SSOV.


13. If the oxygen level rises, it is an indication

that the staged ignition solenoid is stuck, or
is adding gas and preventing the proper
oxygen level from being achieved. The
solenoid will require replacement. Proceed
to step 14.


14. Set the green ON/OFF switch to the OFF

position. Turn off AC power to the unit.


15. Replace the staged ignition solenoid. See

Figure 8.2 for location of the solenoid.


16. Re-open the 1/4” ball valve downstream of

the SSOV.


17. Repeat combustion calibration starting from

step 1 of paragraph 4.3.


18. Once the oxygen level is within the specified

range at 40%, lower the firing rate to 16%.

19. Oxygen levels at the 16% firing rate should

be as shown in Table 2. No adjustment
should be necessary. Contact the Factory if
the oxygen or carbon monoxide levels are
not within the specified range.


NOTE:

If the port being used to sample combustion
products at 16% is too far from the unit, the
readings may be shifted.


Table 2 - Combustion Oxygen Levels for a

16% Firing Rate

Temp (ºF)

O2

CO

NOx (corrected

to 3% O

2

)

130

<20ppm

<20ppm

120

<20ppm

<20ppm

110

<20ppm

<20ppm

100

<20ppm

<20ppm

90

<20ppm

<20ppm

80

<20ppm

<20ppm

70

<20ppm

<20ppm

60

<20ppm

<20ppm

50

<20ppm

<20ppm

40

<20ppm

<20ppm

30

<20ppm

<20ppm

20

<20ppm

<20ppm

10

<20ppm

<20ppm

0

<20ppm

<20ppm

-10

<20ppm

<20ppm

-20

<20ppm

<20ppm

-30

<20ppm

<20ppm

-40

<20ppm

<20ppm

16% Fire Rate

4.5-8.0

5.5-8.5

6.0-9.0

20. Raise the firing rate to 100%. Gas pressure

should still be 4.8” W.C. If it is not, readjust
as necessary. For Benchmark 2.0 Low NOx
boilers configured for De-Rated capacity
(see para. 2.4.1), gas pressure should still
be 3.7” W.C. If not, readjust as necessary.


21. Allow the combustion analyzer to settle.

Compare the measured oxygen level with
the levels in Table 3.

22. If the measured oxygen reading is within the

specified level in Table 3, no further
adjustment is necessary.

23. If the measured oxygen level is not within

specified range in Table 3, adjust the iris
damper as necessary until the measured
oxygen reading is within specification. (See
Figure 4.5).

4-4