INITIAL START-UP

4-5

Table 3 - Combustion Oxygen Levels for

100% Firing Rate

1. Put the green ON/OFF switch in the off

position. Disconnect the AC power supply to
the unit.

Temp (ºF)

O2

CO

NOx (corrected to

3% O

2

)

130

4.3

<100ppm

<40ppm

120

4.5

<100ppm

<40ppm

110

4.7

<100ppm

<35ppm

100

4.8

<100ppm

<30ppm

90

5.0

<100ppm

<30ppm

80

5.1

<100ppm

<30ppm

70

5.1

<100ppm

<30ppm

60

5.2

<100ppm

<30ppm

50

5.3

<100ppm

<30ppm

40

5.4

<100ppm

<30ppm

30

5.4

<100ppm

<30ppm

20

5.4

<100ppm

<30ppm

10

5.4

<100ppm

<30ppm

0

5.4

<100ppm

<30ppm

-10

5.4

<100ppm

<30ppm

-20

5.4

<100ppm

<30ppm

-30

5.4

<100ppm

<30ppm

-40

5.4

<100ppm

<30ppm

100% Fire Rate

2. Shut off the gas supply to the unit.

3. Reinstall the brass hex nut back on the

regulator.

4. Remove all of the manometers and barbed

fittings and reinstall the pipe plugs using a
suitable thread compound.

5. Remove the combustion analyzer probe

from the tapped hole in the exhaust
manifold. Replace the NPT plug previously
removed in para. 4.2.3, step 1.


6. Replace the unit’s panels.

4.5 OVER-TEMPERATURE LIMIT
SWITCH


The over-temperature limit switches are located
on the plate to the left of the boiler shell. One is a
fixed manual reset switch that will shutdown and
lock out the boiler if the water temperature
reaches 210°F. The other is an adjustable auto
reset which allows the boiler to restart, once the
temperature drops below its temperature setting.
Figure 4.6 shows the location of the over
temperature limit switch.

Figure 4.5

Iris Air Damper Location

24. Change the firing rate to 40%. Allow time for

the combustion analyzer to settle. Check the
measured oxygen reading to insure that it is
still within the range as per Table 1.

25. Continue this procedure until oxygen levels

at 40%, 16% and 100% firing rates are
within the ranges specified in Tables 1, 2
and 3.


4.4 UNIT REASSEMBLY

Once combustion calibration is set properly, the
unit can be re-assembled for permanent
operation. Proceed as follows:

Figure 4.6

Over Temperature Limit Switch Location