TROUBLESHOOTING

TABLE 8-1. BOILER TROUBLESHOOTING – Continued

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

continued

4. Defective Air/Fuel Valve stepper

motor.

5. Defective Power Supply Board or

fuse.

6. Defective IGST Board

4. Replace stepper motor.

5. Check DS1 & DS2 LEDs on Power Supply Board. If they are not

steady ON, replace Power Supply Board.

6. Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF

every second. If not, replace IGST Board.




8.2 ADDITIONAL FAULTS WITHOUT SPECIFIC FAULT MESSAGES

Refer to Table 8-2 to troubleshoot faults which may occur without a specific fault message being displayed.

TABLE 8-2. BOILER TROUBLESHOOTING WITH NO FAULT MESSAGE DISPLAYED

OBSERVED INCIDENT

PROBABLE CAUSES

CORRECTIVE ACTION

Hard Light-Off

1. Staged Ignition Ball Valve closed.
2. Clogged/damaged Gas Injector

(Figure 8.2).

3. Defective Staged Ignition Solenoid

(figure 8.2)

1. Open the 1/4” Ball Valve downstream of the SSOV.
2. Remove and inspect Gas Injector to ensure it is not clogged or

damaged.

3. Close the 2” Ball Valve downstream of the Differential Regulator

and the 1/4” Ball Valve downstream of the SSOV. Start the unit
and listen for a “clicking” sound that the Staged Ignition Solenoid
makes during Ignition Trial. If “clicking” sound is not heard after 2
or 3 attempts, replace the Staged Ignition Solenoid.

Fluctuating Gas Pressure

1. Gas pressure going into unit is

fluctuating.

2. Damping Orifice not installed.

1. Stabilize gas pressure going into unit. If necessary, troubleshoot

Building Supply Regulator.

2. Check that the Damping Orifice is installed on the SSOV/

Regulator Actuator (Figure 8.3).

Air/Fuel Valve “hunting” at 80%

Firing Rate

1. IGST and Power Supply Boards

outdated.

1. Check to ensure that the IGST and Power Supply Boards are

Rev. E or higher.

8-10