10 combustion air, 1 combustion air from outside the building, 2 combustion air from inside the building – AERCO BMK 2.0 LN for Mass. only User Manual

Page 21: 3 sealed combustion

Advertising
background image

INSTALLATION

2-9

NOTE:

Both the Delayed Interlock and Remote
Interlock must be in the closed position to
allow the unit to fire.

2.7.9.1 REMOTE INTERLOCK IN

The remote interlock circuit (REMOTE INTL’K
IN) is provided to remotely start (enable) and
stop (disable) the Boiler if desired. The circuit is
24 VAC and comes factory pre-wired closed
(jumped).

2.7.9.2 DELAYED INTERLOCK IN

The delayed interlock circuit (DELAYED INTL’K
IN) is typically used in conjunction with the
auxiliary relay described in paragraph 2.8. This
interlock circuit is located in the purge section of
the start string. It can be connected to the
proving device (end switch, flow switch etc.) of
an auxiliary piece of equipment started by the
Boiler’s auxiliary relay. The delayed interlock
must be closed for the boiler to fire. If the
delayed interlock is connected to a proving
device that requires time to close (make), a time
delay (Aux Start On Dly) that holds the start
sequence of the boiler long enough for a proving
switch to make can be programmed. Should the
proving switch not prove within the programmed
time frame, the boiler will shut down. The Aux
Start On Dly can be programmed from 0 to 120
seconds. This option is locate in the Configura-
tion Menu (Chapter 3).

2.7.10 FAULT RELAY

The fault relay is a single pole double throw
(SPDT) relay having a normally open and
normally closed set of relay contacts that are
rated for 5 amps at 120 VAC and 5 amps at 30
VDC. The relay energizes when any fault
condition occurs and remains energized until the
fault is cleared and the CLEAR button is
depressed. The fault relay connections are
shown in Figure 2.9

2.8 AUXILIARY RELAY CONTACTS

Each Boiler is equipped with a single pole
double throw (SPDT) relay that is energized
when there is a demand for heat and de-
energized after the demand for heat is satisfied.
The relay is provided for the control of auxiliary
equipment, such as pumps and louvers, or can
be used as a Boiler status indictor (firing or not
firing). Its contacts are rated for 120 VAC @ 5
amps. Refer to Figure 2.9 to locate the AUX
RELAY terminals for wiring connections.

2.9 FLUE GAS VENT INSTALLATION

The AERCO Venting and Combustion Air Guide,
GF-2050, must be consulted before any flue gas
vent or inlet air venting is designed or installed.
U/L listed, positive pressure, watertight vent
materials as specified in AERCO’s GF-2050,
must be used for safety and code compliance.
Because the unit is capable of discharging low
temperature exhaust gases, the flue must be
pitched back to the unit a minimum of 1/4" per
foot to avoid any condensate pooling and to
allow for proper drainage.

The combined pressure drop of vent and
combustion air systems must not exceed 140
equivalent feet of 8 inch ducting. Fittings as well
as pipe lengths must be calculated as part of the
equivalent length.

For a natural draft installation the draft must not
exceed -0.25”/+0.25" W.C. These factors must
be planned into the vent installation. If the
maximum allowable equivalent lengths of piping
are exceeded, the unit will not operate properly
or reliably.

The Heatfab Division of the Selkirk Corporation
provides vent systems which conform to all
applicable requirements for installations within
the Commonwealth of Massachusetts. Contact
information for this supplier are as follows:

Selkirk Corporation
Heatfab Division
130 Industrial Blvd.
Turners Falls, MA 01376
Phone: 1-800-772-0739
www.heat-fab.com

2.10 COMBUSTION AIR

The AERCO Venting and Combustion Air Guide,
GF-2050, MUST be consulted before any flue or
combustion supply air venting is designed or
started. Combustion air supply is a direct
requirement of ANSI 223.1, NFPA-54, and local
codes. These codes should be consulted before
a permanent design is determined.

The combustion air must be free of chlorine,
halogenated hydrocarbons, or other chemicals
that can become hazardous when used in gas-
fired equipment. Common sources of these
compounds are swimming pools, degreasing
compounds, plastic processing and refrigerants.
Whenever the environment contains these types
of chemicals, combustion air must be supplied
from a clean area outdoors for the protection
and longevity of the equipment.

Advertising