INITIAL START-UP

It is important to perform the following procedure
as outlined. This will keep readjustments to a
minimum and provide for optimum performance.

1. Open the water supply and return valves to

the unit and ensure that the system pumps
are running.


2. Open the natural gas supply valve to the

unit.

3. Set

the

ON/OFF switch in the OFF position.

Turn on AC power to the unit. The display
will show LOSS OF POWER and the time
and date.

4. Set the unit to the Manual Mode by pressing

the AUTO/MAN key. A flashing Manual Fire
Rate
message will be displayed with the
present rate in %. Also, the MANUAL LED
will light.

5. Adjust the rate to 0% by pressing the ▼

arrow key.

6. Ensure that the 1/4” ball valve downstream

of the SSOV is open.


7. Set the ON/OFF switch to the ON position.

Change the fire rate to 40% using the
arrow key. The unit should begin its start
sequence and fire.

8. Next, gradually increase the firing rate to

100% in 20% increments and verify that the
gas pressure downstream of the SSOV is
4.8” W.C. for both FM and IRI gas trains at
100% firing rate. If not, remove the brass
hex nut on the droop eliminator using the
black plastic wrench from the Iris Damper.
Make the droop eliminator adjustment using
a flat-tip screwdriver to obtain 4.8” W.C (see
Figure 4.4). For Benchmark 2.0 Low NOx
boilers configured for De-Rated capacity
(see para. 2.4.1), the gas pressure
downstream of the SSOV must be 3.7” W.C.
for both FM and IRI gas trains at a 100%
firing rate.


CAUTION:

Turn the droop eliminator adjustment screw
very slowly. Unlike ordinary regulators, this
adjustment is very sensitive.


DROOP ELIMINATOR
ADJUSTMENT SCREW

Figure 4.4

Adjustment Screw Location

9. Lower the firing rate to 40% using the

arrow key. Insert the combustion analyzer
probe into the exhaust manifold and allow
enough time for the combustion analyzer to
settle. Compare the measured oxygen level
to the oxygen range for inlet air temperature
in Table 1.

10. If needed, adjust the differential regulator

until the oxygen reading is within the
specified range in Table 1.

NOTE:

Adjust only the differential regulator at 40%
control signal. Do not adjust the iris air
damper.

Table 1 - Combustion Oxygen Levels for a

40% Firing Rate

40% Fire Rate

Temp (°F)

O2

CO

NOx (corrected to

3% O

2

)

130 4.6

<30ppm <20ppm

120 4.8

<30ppm <20ppm

110 5.0

<30ppm <20ppm

100 5.2

<25ppm <20ppm

90 5.3

<25ppm <20ppm

80 5.5

<25ppm <20ppm

70 5.6

<25ppm <20ppm

60 5.9

<25ppm <20ppm

50 6.2

<25ppm <20ppm

40 6.4

<25ppm <20ppm

30 6.5

<25ppm <20ppm

20 6.5

<25ppm <20ppm

10 6.5

<25ppm <20ppm

0 6.6

<25ppm

<20ppm

-10 6.6

<25ppm <20ppm

-20 6.7

<25ppm <20ppm

-30 6.8

<25ppm <20ppm

-40 6.8

<25ppm <20ppm

4-3