MAINTENANCE

Table 7-1. - Maintenance Schedule

PARAGRAPH

ITEM

6 Mos.

12 Mos.

24 Mos.

Labor

Time

7.2

Spark Igniter

(GP-122435-S)

*Inspect Inspect Replace 15

mins.

7.3

Flame Detector

(66006)

*Inspect Inspect Replace 15

mins.

7.4

Combustion

Adj.

*Check Check

1

hr.

7.5

Testing of

Safety Devices

See CSD-1

Chart in

Appendix

I

20 mins.

7.6 Burner Inspect

2

hrs.

7.7

Condensate

Drain Trap

Inspect

Inspect &

Clean

1

hr.

* Only performed after initial 6 month period after initial startup.

7.3 FLAME DETECTOR

The flame detector, part number 66006, is
located in the body of the burner (see Fig. 7.1).
The flame detector may be HOT. Allow the unit
to cool sufficiently before removing the flame
detector.

To inspect or replace the flame detector:

1. Set

the

ON/OFF switch on the control panel,

to the OFF position. Disconnect AC power
from the unit.


2. Remove the top panels from the unit.

3. Disconnect the flame detector lead wire.

Unscrew the flame detector and remove it.
(See Fig 7.2)


4. Inspect the detector thoroughly. If eroded,

the detector should be replaced. Otherwise
clean the detector with a fine emery cloth.


5. Reinstall the flame detector and flame detec-

tor gasket, if removed.


6. Reconnect the flame detector lead wire.

7. Reinstall the side and top panels on the unit.

7.4 COMBUSTION CALIBRATION

Combustion settings must be checked at the
intervals shown in Table 7-1 as part of the
maintenance requirements. Refer to Chapter 4
for combustion calibration instructions.


Figure 7.2

Spark Igniter and Flame Detector Location

Cut-Away View

7-2