CONTROL PANEL OPERATING PROCEDURES

Table 3-4. Configuration Menu - Continued

Available Choices or Limits

Menu Item Display

Minimum

Maximum

Default

Failsafe Mode

Shutdown or Constant Setpt

Shutdown

*mA Output
(See CAUTION)

Setpoint, Outlet Temp,

Fire Rate Out, Off

*Fire Rate

Out

Low Fire Timer

2 sec.

120 sec.

2 sec.

Setpt Limiting

Enabled or Disabled

Disabled

Setpt Limit Band

0°F

10°F

5°F

*CAUTION

: DO NOT CHANGE mA Output Menu Itemfrom its Default setting.

3.7 TUNING MENU

The Tuning Menu items in Table 3-5 are Factory
set for each individual unit. Do not change

these menu entries unless specifically requested
to do so by Factory-Trained personnel.

Table 3-5. Tuning Menu

Available Choices or Limits

Menu Item Display

Minimum

Maximum

Default

Prop Band

1°F

120°F

70°F

Integral Gain

0.00

2.00

1.00

Derivative Time

0.0 min

2.00 min

0.00 min

Reset Defaults?

Yes

No

Are You Sure?

No

3.8 START SEQUENCE

When the Control Box ON/OFF switch is set to
the ON position, it checks all pre-purge safety
switches to ensure they are closed. These
switches include:

• Safety Shut-Off Valve Proof of Closure

(POC) switch

• Low Water Level switch
• High

Water

Temperature

switch

• High Gas Pressure switch
• Low Gas Pressure switch
• Blower Proof switch

If all of the above switches are closed, the
READY

light above the ON/OFF switch will light

and the unit will be in the Standby mode.

When there is a demand for heat, the following
events will occur:

NOTE

If any of the Pre-Purge safety device
switches are open, the appropriate fault
message will be displayed. Also, the
appropriate fault messages will be displayed
throughout the start sequence, if the
required conditions are not observed.

1. The

DEMAND

LED status indicator will light.

2. The unit checks to ensure that the Proof of

Closure (POC) switch in the downstream
Safety Shut-Off Valve (SSOV) is closed.
See Figure 3-3 for SSOV locations.


3-7