INSTALLATION

SHELL

CAP

PARTIAL TOP VIEW OF BOILER

FOR INSTALLATION OF PRESS./TEMP. GAUGE

PART NO. 122994-1 (PRESS. RANGE 0 – 75 PSI)

SYSTEM

SUPPLY

1/2" x 1 /4"

REDUCING BUSHING

PRESS./TEMP. GAUGE

Figure 2.5a

Pressure /Temperature Gauge Installation

Figure 2.5b

Pressure/Temperature Gauge Installation

2.3.5 CONDENSATE PIPING

The KC Boiler is designed to condense.
Therefore, the installation site must include
suitable provisions for condensate drainage or
collection. A stainless steel condensate cup is
separately packed within the unit’s shipping
container. To install the condensate cup,
proceed as follows:

1. Remove the left side panel and only the left

half of the rear cover to provide access to the
exhaust manifold and burner (Figure 2.6).

2. Insert the 1-3/4 inch manifold drain hose into

the condensate cup. Allow the cup to rest on
the floor directly beneath the manifold drain
hole (Figure 2.6).

3. Attach a length of 3/4 inch I.D. polypropylene

tubing to the condensate cup drain tube and

route it to a floor drain. If a floor drain is not
available, a condensate pump can be used to
remove the condensate to drain. The
condensate drain line must be removable for
routine maintenance. Therefore, DO NOT hard-
pipe.

4. Replace the rear cover and side panel on the

unit.

Figure 2.6

Condensate Drain System Location

2.4. GAS SUPPLY PIPING

The AERCO

Gas Fired Equipment Gas Compo-

nents and Supply Design Guide (GF-1030) must be
consulted before any gas piping is designed or
started.

WARNING!

DO NOT USE MATCHES, CANDLES,
FLAMES OR OTHER SOURCES OF
IGNITION TO CHECK FOR GAS LEAKS

.

CAUTION!

Soaps used for gas pipe leak testing can be
corrosive to metals. Piping must be rinsed
thoroughly with clean water after leak
checks have been completed.

NOTE:

All gas piping must be arranged so that it
does not interfere with removal of any
cover, inhibit service or maintenance, or
prevent access between the Unit and walls,
or another unit.