Appendix a – AERCO KC1000 Boiler equipped with C-More version 3.04 User Manual

Page 73

Advertising
background image

APPENDIX A

APPENDIX A -

BOILER MENU ITEM DESCRIPTIONS - Continued

MENU LEVEL & OPTION

DESCRIPTION

CONFIGURATION MENU (Cont.)

Reset Ratio

Permits setting of Reset Ratio when operating boiler
in the Outdoor Reset Mode. Reset Ratio is
adjustable from 0.1 to 9.9. Default is 1.2.

Outdoor Sensor

Allows outdoor sensor function to be enabled or
disabled. Default is disabled.

System Start Tmp

If outdoor sensor is enabled, this menu item allows
the system start temperature to be set from 30 to
100°F. Default is 60°F.

Setpoint Lo Limit

Used to set the minimum allowable setpoint (40°F to
Setpoint Hi Limit). Default is 60°F

Setpoint Hi Limit

Used to set the maximum allowable setpoint
(Setpoint Lo Limit to 240°F). Default is 200°F.

Temp Hi Limit

This is the maximum allowable outlet temperature
(40 to 240°F). Any temperature above this setting
will turn off the unit. The temperature must then
drop 5° below this setting to allow the unit to run.
Default Hi Limit is 210°F.

Max Valve Positon

Sets the maximum allowable valve position for the
unit (40% to 100%). Default is 100%.

Pump Delay Timer

Specifies the amount of time (0 to 30 min.) to keep
the pump running after the unit turns off. Default is
zero.

Aux Start On Dly

Specifies the amount of time to wait (0 to 120 sec.)
between activating the Aux Relay (due to a
demand) and checking the pre-purge string to start
the boiler. Default is 0 sec.

Failsafe Mode

Allows the Failsafe mode to be set to either
Constant Setpoint or Shutdown. Default is
Shutdown.

Analog Output

Must be set to Valve Pos 0-10V.

Lo Fire Timer

Specifies how long (2 to 600 sec.) to remain in the
low fire position after ignition, before going to the
desired output. Default is 2 sec.

Network Timeout

Specifies the timeout value (seconds) before a
Modbus fault is declared. Available settings range
from 5 to 999 seconds. Default is 30 seconds.

A-3

Advertising