Secondary menu item descriptions – AERCO KC1000 Boiler equipped with Mod-Box Controller User Manual

Page 58

Advertising
background image

APPENDIX A

ii

SECONDARY MENU ITEM DESCRIPTIONS

CONSTANT SETPOINT



FUNC








OSAT






Oat





LLT





Hlt





Pb1







Int

This indicates the mode of operation the
temperature controller is in. Common
modes are Oart, indoor\outdoor reset,
Cont, constant setpoint, and FDFO for a
water heater.



This menu item turns the outside air
enable\disable feature on or off. When
ON, an outside air temperature can be
chosen to enable or disable the unit.


This displays the outside air
temperature that the unit is enabled.
This parameter is displayed only when
OSAT is on.


This is Low Limit Temperature alarm.
This will put the temperature controller
into alarm if the outlet water
temperature goes below this setting.


This is High Limit Temperature alarm.
This will put the temperature controller
into alarm if the outlet water
temperature exceeds this setting.


This is the Proportional Band in

0

F for

the feedback of the controller. This
feature is useful in correcting outlet
temperature errors when under steady
load conditions.



This is the integral rate, in minutes, for
the feedback of the controller. It is
adjusted with the× and Ø. Press
ENTER to accept changes.

Advertising