SPECIFICATIONS: (continued)

Model

Number

MLX-303 MLX-454 MLX-606 MLX-757 MLX-909

MLX-1060

Water Pressure Drop @
Max. Flow

5 psi

(34.5 kPa)

6 psi

(41.4 kPa)

9 psi

(62.1 kPa)

10 psi

(68.9 kPa)

13 psi

(89.6 kPa)

15 psi

(103.4 kPa)

Water Volume: Gallons

2.7

3.8

4.9

6.0

7.1

8.2

Water

Volume:

Liters

10.2 14.4 18.5 22.7 26.9 31.0

Thermal

Modules

2 3 4 5 6 7

Turn-Down

Ratio

6:1 10:1 13:1 16:1 20:1 23:1

Vent Size

4” (102 mm) 4” (102 mm) 4” (102 mm) 6” (152mm) 6” (152mm) 6” (152mm)

Vent Materials (per local
code)

Can support PVC, ABS, CPVC, or AL29-4C venting materials.

Temperature Control
Range

All units can be applied to deliver 50°F to 185°F (10°C to 85°C) supply water.

Maximum Noise Level

All units deliver <50 dBA when operating at or below full fire.

NOx Emissions
Certification

All units have been certified by SCAQMD and TCEQ for <30 ppm NOx.

Standard Listings &
Approvals

All units have been certified by CSA.

1.6 MODULEX SIDE VIEW SHOWING MAIN COMPONENTS