6 - boiler operation, Boiler operation – AERCO Modulex General Manual User Manual

Page 35

Advertising
background image

INSTALLATION, OPERATION & MAINTENANCE

6-1

BOILER OPERATION

6.1 GENERAL DESCRIPTION AND OPERATION

The Modulex is a cast aluminum body boiler consisting of mutually connected combustion chambers,
each having its own burner, blower and air pressure switch, gas valve, ignitor and flame detection.
Each group of these components is referred to as a module.

The boiler has supply and return temperature sensors that the System (E8) Manager uses to monitor
total outlet temperature from each module and the system return water temperatures before being
redistributed to each module. These sensors are negative temperature coefficient (NTC) sensors and
are designated the Global Flow Sensor for the supply sensor and the Global Return for the return
sensor (see Figures 2-4 and 2-6). Each module has its own temperature sensor called the Local Flow
NTC, which monitors the water temperature of each module. The water temperature measured by the
Local NTC sensor is compared to the return supply water temperature. If for any reason the
temperature difference between the Local Flow and the Global Return temperatures becomes greater
than 54°F (30°C), the module or modules will begin to modulate as follows:

0°F to 54°F (0°C to 30°C)

Normal Operation

54°F to 63°F (30°C to 35°C)

Burner will begin Modulating down

63

o

F to 72

o

F (35°C to 40°C)

Burner will stay at 45,500 BTU’s

Above 72°F (40°C)

Burner will shut off


The variable speed fan's pressure drives the gas valve to allow gas to enter into the pre-combustion
chamber where it mixes with the combustion air. The mixed air and gas pass thru the check valve on to
the burner surface for ignition. Combustion gases pass thru the heat transfer surfaces. Flue gases and
condensate then exit the heat exchanger entering into the condensate tray.

6.2 MODULATION THEORY

One of the operating principles for this boiler is to have as many modules as possible operate
simultaneously at minimum load to reach the maximum efficiency. This is maintained by the System
Manager (E8) which determines a percent of modulation based on the difference between the set point
temperature and the actual supply water (global flow) temperature. This operating principle provides
efficiencies much higher than those obtained in traditional groups of small boilers installed in cascade.

Each of the boiler’s modules represents a maximum output of 151.5 MBH (44.4 kW). The number of
modules x 100% determines the maximum output expressed in percent. For example, if a four module
boiler is requested to operate at its max output, this shall be 400% i.e.

151.5 MBH (44.4 kW) x 4 modules =606 MBH (177.6 kW) = 400%.

If the required percentage is 200%, each module will operate at 50% output. This equals a total of 303
MBH (88.8 kW) out of a possible 606MBH (177.6 kW), and each module will be operating at 75.75
MBH (22.2 kW) out of a possible 151.5 MBH (44.4 kW).

When the output shared on each module is less than approximately 30%, one module after the other is
automatically turned off and the remaining output is shared on modules having the smallest number of
operation hours (by the automatic operation-time calculating system).

6

Advertising