Electronic Control System (ECS) and Type CXT-E Valve

3. ADJUSTMENT

Page 26 of 82

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

VD2: 02/28/14

OMM-0003_0D

AC-105

NOTE:

DO NOT PRESS THE RESET BUTTON before the 10 second period
has ended.

Blinks

Valve Size

1

1”

2

1.25” and 2.5”

3

1.5” and 3”

4

2” and 4”


5) For Full-Stroke automatic adjustment, press the Reset button. The LED will light.

6) The Actuator will then rotate in both directions to find its open and closed Valve position

stops.

7) Upon successful completion of the automatic adjustment, the LED will blink 1 to 4 times

(depending on the valve size shown above) and then go off.

8) Replace and secure the Actuator cover by tightening the set screw.

0

90

neptronic

1 2 3

1

2

3

4

5

1

2

3

DIP SWITCHES (3)

(ALL IN UP POSITION)

AUTO-STROKE

(RESET) BUTTON

LED

TERMINALS

PC BOARD

COVER
SET SCREW

ACTUATOR

Figure 3-1. Actuator Adjustment