7. TROUBLESHOOTING

Page 46 of 82

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

VD2: 02/28/14

OMM-0003_0D

AC-105

Table 7-2. Troubleshooting – Electronic Control System (ECS)- Continued

NO.

FAULT

INDICATION

PROBABLE CAUSE

CORRECTIVE ACTION

T13

Wide
fluctuations
in outlet
water
temperature
under low
flow
conditions.

1. Outlet Temp Sensor

connected to Temp
Controller is intermittent

2. Obstruction in Flow

Sensor.

3. Inlet Orifice worn or not

properly seated.

4. Recirculation Pump

failure.

1. Replace Outlet Temp Dual Sensor

at Heater outlet port.

2. Clean or refurbish Flow Sensor per

Section 6.

3. Replace Orifice or reseat in required

nozzle position.

4. Replace Recirculation Pump.

T14

Temp
Controller
displays
Loop break
(Lbr) error
message

1. Outlet Temp Sensor not

connected.

2. Outlet Temp Sensor

defective.

1. Ensure Temp Sensor connector

plug is securely connected.

2. Replace Outlet Temp Dual Sensor

installed at Heater outlet port.

T15

Outlet water
temperature
above Over-
Temp Limit,
but Solenoid
(Dump)
Valve does
not open.

1. Disconnected or

defective Solenoid



2. Defective Over-Temp

Switch

1. Verify that 24 VDC is present at

Solenoid plug between leads
103(+) and 104 (-).
If voltage is present and Solenoid is
connected, it is defective and must
be replaced. If 24 VDC is not
present, go to item 2.

2. Replace Over-Temp Switch.

T16

Inconsistent
temperature
reading

1. Sensor wire polarity

reversed.


2. Faulty Sensor.

1. Check polarity of TC wiring; J

Thermocouple Standard Wiring:
-- Red wire is negative.
-- White wire is positive.

(Refer to Wiring Diagram B-2)

2. Replace TC Sensor.

OPEn

Secondary
Input is
missing.

g

1. Flow meter not powered.

2. Failed feedforward sensor.

3. Unplugged connection to

feedforward sensor.

1. Check power LED of Flow meter. Apply

power or replace.

2. Replace feedforward sensor.

3.

Ensure proper sensor connections.

Advertising