AERCO ECS Retrofit User Manual

Page 48

Advertising
background image

48

4.5.1 Helitherm Steam-to-Water Units
For Helitherm Steam-to-Water units, refer to Figure 4-11 which shows a typical B-Plus Heater.
Proceed as follows:

1. Remove the Compound Pressure Gauge (8356-[ ]), Pig Tail (8-20) and 1/4” Coupling (9-3)

from the Retrofit Kit.

2. Install the Pig Tail in the tapped hole downstream of the CXT-E Control Valve.

3. Attach the 1/4” NPT Coupling and Pressure Gauge to the Pig Tail as shown in Figure 4-11.

Tighten all connections.

4.5.2 Double Wall Steam-to-Water Units
For Double-Wall Steam-to-Water units, refer to Figure 4-12. This Figure shows typical Compound
Pressure Gauge installation locations for DW-24 and DW-68 units.

1. Remove the Compound Pressure Gauge (8356-[ ]), Pig Tail (8-20), 1/4” NPT x 4” long Nipple

(91024) and two 1/4” NPT Couplings (9-3) from the Retrofit Kit.

2. For a DW-24 unit, install the 4” long NPT Nipple to the existing elbow on the Steam Inlet. For

DW-68 or DW-45 units, install the 4” long NPT Nipple to the Steam Inlet Flange.

3. Next install one of the 1/4” Couplings to the end of the 4” long Nipple.

4. Attach the Pig Tail, 1/4” Coupling and Compound Pressure Gauge as shown in Figure 4-12.

Tighten all connections

Advertising