Figure 2.5, Condensate drain assembly location, Figure 2.6 – AERCO KC1000 Heater w/Mod-Box Controller User Manual

Page 10: Installation procedures

Advertising
background image

INSTALLATION PROCEDURES

5

Figure 2.5

Condensate Drain Assembly Location

2.4 GAS SUPPLY PIPING
AERCO Gas Fired Equipment Gas Components
and Supply Design Guide (GF-1030) should be
consulted before any gas piping is designed or
started.

WARNING !

DO NOT USE MATCHES, CANDLES,

FLAMES OR OTHER SOURCES OF

IGNITION TO CHECK FOR GAS LEAKS

.

CAUTION !

Many soaps used for gas pipe leak testing

are corrosive to metals. The piping must be

rinsed thoroughly with clean water after

leak checks have been completed

.

NOTE:

All gas piping must be arranged so that it

does not interfere with removal of any

cover, inhibit service or maintenance, or

prevent access between the unit and walls,

or another unit

.

The location of the 1-1/4" inlet gas connection
on the right side of the unit is shown in Figure
2.6.

All pipe should be de-burred and internally
cleared of any scale or iron chips before
installation. No flexible connectors or non-
approved gas fittings should be installed. Piping
should be supported from floor or walls only and
must not be secured to the unit.

A suitable piping compound approved for use
with gas should be used sparingly. Any excess
must be wiped off to prevent clogging of
components.

To avoid damage to the unit when pressure
testing gas piping, isolate the unit from the gas
supply piping. At no time should there be more
than 1 psig maximum to the unit. Bubble test all
external piping thoroughly for leaks using a soap
and water solution or suitable equivalent. The
gas piping must meet all applicable codes.

Figure 2.6

Gas Supply Regulator and Manual Shut -

Off Valve Location

2.4.1 GAS SUPPLY PRESSURE REGULATOR
A mandatory external, in line, supply gas
regulator (supplied by others) should be
positioned as shown in Figure 2.6. Union
connections should be placed in the proper
locations to allow maintenance of the regulator if
required.

NOTE:

An individual gas pressure regulator must

be installed upstream of each unit. The

regulator must regulate gas pressure to

8.5” W.C. for FM gas train and 8.9” W.C. for

IRI gas trains at 1,000,000 BTU/H for

natural gas and propane units.

The maximum static inlet pressure to the unit
must be no more than 14” water column.
Minimum gas pressure is 8.5” W.C. for FM gas
trains and 8.9” W.C. IRI gas trains when the unit
is firing at maximum input. Gas pressure should

Advertising